APC 1000VA user manual On Battery Operation

Page 9

AVR Trim

AVR Boost

On Battery

Overload

Replace Battery

Battery

Disconnected

Automatic Self-Test

Manual Self-Test

This LED illuminates to indicate the UPS is compensating for a high utility voltage.

This LED illuminates to indicate the UPS is compensating for a low utility voltage.

When the on battery power LED is lit the UPS is supplying battery power to the connected equipment. When on battery, the UPS sounds an alarm—four beeps every 30 seconds.

The LED illuminates and the UPS emits a sustained alarm tone when an overload condition occurs.

Failure of a battery self-test causes the UPS to emit short beeps for one minute and the replace battery LED illuminates. Refer to Trouble- shooting in this manual.

The replace battery LED flashes and short beep is emitted every two seconds to indicate the battery is disconnected.

The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default).

During the self-test, the UPS briefly operates the connected equipment on battery.

If the UPS fails the self-test, the replace battery LED lights and immediately returns to online operation. The connected equipment is not affected by a failed test. Recharge the battery for 24 hours and per- form another self-test. If it fails, the battery must be replaced.

Press and hold the button for a few seconds to initiate the self-test.

On Battery Operation

The Smart-UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.

Press the button (front panel) to silence the UPS alarm (for the current alarm only). If the utility power does not return, the UPS continues to supply power to the connected equipment until the bat- tery is exhausted.

If PowerChute is not being used you must manually save your files and power down before the UPS turns off.

DETERMINING ON BATTERY RUN TIME

UPS battery life differs based on usage and environment. It is recommended that the battery/batteries be changed once every three years. See the APC web site, www.apc.com, for on battery run times.

7

Image 9
Contents APC Smart-UPS Page Introduction UnpackingPositioning the UPS Installing the Rails in the Rack Mounting the UPS in a Rack Connecting Equipment and Power to the UPS UPS. Use only interface kits supplied or approved by APC Operation On Battery Operation User Configurable Items 230V models Replacing the Battery Module Disconnecting the Battery for TransportStorage Troubleshooting 120V models only. Site wiring Utility Voltage Contacting APC Service230V Models Regulatory Agency Approvals and Radio Frequency WarningsDeclaration of Conformity Limited Warranty
Related manuals
Manual 1 pages 62.02 Kb

1000VA specifications

The APC 1000VA is a robust uninterruptible power supply (UPS) designed to provide reliable backup power and surge protection for small to medium-sized office equipment. This device is especially critical for safeguarding sensitive electronics such as computers, networking equipment, and telecommunication systems from unexpected power outages and fluctuations.

One of the standout features of the APC 1000VA is its high-capacity output of 1000 volt-amperes (VA), ensuring that it can handle the power demands of multiple devices simultaneously. The UPS delivers a pure sine wave output, which mimics the utility power supply, ensuring greater compatibility with a wider range of sensitive electronics. This feature is particularly beneficial for equipment that requires stable power input to function optimally.

In terms of connectivity, the APC 1000VA is equipped with several outlets, allowing users to connect multiple devices while providing sufficient backup power during outages. The UPS also features USB and serial communication ports, enabling users to interface the unit with computers for monitoring and management purposes. This integration allows for automatic shutdown software, which protects data integrity by safely powering down devices during extended outages.

The APC 1000VA incorporates advanced battery management technologies, including automatic battery testing and smart battery charging, which extend the life of the internal batteries and improve overall performance. The unit is designed to easily maintain its battery health, minimizing the need for frequent replacements and reducing long-term ownership costs.

With a compact design, the APC 1000VA is easy to install and fits well in various environments, from home offices to small business settings. The audible alarms provide alerts for power conditions, ensuring users are always aware of their power scenario.

In addition to these features, the APC 1000VA includes essential safety protections such as overload protection, short-circuit protections, and temperature-regulated battery charging. These safety measures contribute to the reliability and longevity of the UPS.

Overall, the APC 1000VA combines performance, versatility, and reliability, making it an ideal choice for anyone needing an efficient power backup solution to protect vital equipment from power irregularities. With its solid construction and reliable technology, it stands out as a dependable ally in maintaining power continuity in various settings.