5.Once the installation is complete, use a 3/4 inch wrench to screw down the UPS leveling feet located next to the four casters, until the unit is no longer resting on the casters.

6.The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that are operating near by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or powered from a different source than that of the affected equipment.

WARNING

THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.

7.It is the responsibility of the installer of this equipment to provide a suitable disconnect for the Control Panel supplying power to this equipment.

This disconnect must:

Be suitable for the Voltage and Full Load Ampere Rating of all downstream equipment supplied by the Panel;

The supply disconnecting device shall be one of the following types:

Switch-disconnector, with or without fuses, in accordance with IEC 60947-3, utilization category AC-23B or DC-23B

As above, except one that has an auxiliary contact that in all cases causes switching devices to break the load circuit before the opening of the main contacts of the disconnector.

A circuit breaker suitable as an isolation device per IEC 60947-2

Any other switching device in accordance with an IEC product standard that also meets the isolation requirements of IEC 60947-1 and is appropriate for on-load switching of motors or other inductive loads;

Be approved for use as a disconnect for the country in which this equipment is installed. Be provided with a Lock Out Tag Out capability in the Off (Down) position.

8.Allow 5 minutes after power is removed for internal capacitors to fully discharge before attempting to service the unit.

9.The user should provide output over-current protection for hardwired UPS systems. See Specifications section on pages 19 and 22 for the device rating.

10.After ensuring that all power sources are turned off and isolated in accordance with established lockout/tagout procedures, connect the power source wiring of the correct voltage to the input terminals of the UPS.

11.The end user must supply suitable strain relief for the power cord and the cord must extend a distance of 1/2 diameter beyond the clamp.

12.Connect the output terminals of the UPS to the load in line with local wiring regulations. Size the branch circuit conductors in accordance with NEC Table 310.16.

8

1600XP Series Installation and Operation Manual

Image 16
Contents 1600XP Series Page 60616-005 April Product Use and Warranty Restrictions Qualified Personnel onlyUninterruptible Power System UPS Purpose Toshiba Customer Support CenterToshiba Customer Support Center Toshiba International CorporationTable of Contents Screen Tab Monitor Screen Tab Settings Preventive Maintenance/Parts ReplacementExternal Layouts/Dimensions/Shipping Weights Display and KeysSymbols General Safety InstructionsProhibited Symbol indicates do not take action Signal Words Regulatory Compliance StatementFCC Class a Notice EMC Directive Class a Note20 a 45 a 60 a 80 a 100 a 125 a144 Vdc 216 Vdc 288 Vdc Qualified personnel shallInstructions Importantes Concernant LA Sécurité To be performed by Qualified Personnel OnlyPower Backup Power ConditioningProduct Description Application and UseInspection/Storage/Disposal InspectionUnpacking StorageInstallation Precautions UPSMetal of Conduit is not AN Acceptable Ground Operating Precautions Conductor Routing and GroundingEquipment Warning Labels Sheet 14 15 16 Connections Terminal BlockWire Size and Tightening Torque Number KVA 10 kVA 14-18 kVA 22 kVA Lb.-in. NmOptional Battery Cabinet Connections UPS Model Battery Cabinet Mccb CapacityMA rms Vac peak MA peak Pin Signal Function Logic UPS Communication InterfacesRemote Contacts Current Vdc peak MA peakUPS LAN Shutdown Signal Operation RS-232C Pin Symbol DescriptionRemotEye III Network Card UPS Specifications Unit Capacity 6kVA 3.1 kW KVA 5.1 kW KVA 6.8 kW KVA 8.5 kWStandard Models 3.6 10 kva cont’d Battery System Battery Replacement YuasaCapacity KVA 11.9 kW1 KVA 15.3 kW1 KVA 18.7 kW1 Standard Models 14 22 kva cont’d Toshiba Part Number for 51896-FS 60995-FS Battery Pack Capacity KVA 11.9 kW1 KVA 15.3 kW1 KVA 18.7 kW 1Command Options Battery Low Voltage Tolerances Battery Backup Time and Discharge ProcessUPS Capacity Starting/Stopping the UPS Stopping the UPSBattery Recharging On-Line Run operation Operating ModesStatic-Bypass Stop operation Battery Backup On batteries EPO Emergency Power Off FunctionAudible Alarm Functions ConditionFront Panel Layout Display and KeysDisplay Manual Controls 1600 XP Monitor and Settings screens Operating KeysRecords screens BATLight Emitting Diodes LED Status IndicatorsEnd Test Faults Operation Input Bypass Batt History Backup SystemTouchscreen Menu Tree Output DC Bus Ctrl/Cfg Disp/ReyeScreen Tab Main RUN/Stop the UPSKeypad Controls Change Secu. LvlQuit WriteScreen Security Passwords & Keypad LoginMimic Display Screen Tab MonitorMonitor Details Mimic Display Settings Screen Tab SettingsKey Cmd ID range Types of Parameters DISP/Reye Block Changing UPS Parameter Settings 240VRecalibrate the Touchscreen Settings Parameters Access Level Sec. AbbreviationUSR ADMOn LCD Tab BlockToshiba Toshiba H3On LCD ERR OUTBYP Batt 503 Discharge Cur Battery Discharge Current Monitor RUN StopDvcoh ViovUSER, Admin AdminLansd Hist 704 UPS Lifetime UPS Lifetime Remaining Time Settings 719 Total Warnings Total No. Of Warning Settings On LCD On LCD Records Sample record screensSystem Fault Messages Display Meaning ActionSystem Warning Messages Bypuv CallDcer DdcnSystem Status Messages System Mode MessagesDisplay Meaning Pfail RmtsdRO2EEERR SyncSystem Protection Features UPS Protection SystemSystem Protection Functions Overheating Overcurrent Current Limit OverloadPreventive Maintenance/Parts Replacement Preventive MaintenanceCleaning the Touchscreen Overvoltage OvercurrentParts Replacement Optional Receptacle Panel Installation InstructionsBatt Amb Temp Average lifetime      Internal Maintenance Bypass Optional MB Maintenance Bypass UnitsLED OFF External Maintenance Bypass External Layouts/Dimensions/Shipping Weights Dimensional DataUnit and Shipping Weights Electrical Conduit Knock-out DataExternal Layout for 3.6kVA and 6kVA units Snmp Port Remote Eye Slot Page Index Page Page UPS Page Industrial Division
Related manuals
Manual 100 pages 60.45 Kb

1600XP specifications

The Toshiba 1600XP is an advanced multifunction printer that showcases Toshiba's commitment to innovation and reliability in office technology. Designed to meet the demands of modern businesses, the 1600XP integrates several features and technologies that enhance productivity while ensuring high-quality output.

One of the key characteristics of the Toshiba 1600XP is its impressive speed. Capable of printing up to 16 pages per minute, this printer is well-suited for busy work environments where efficiency is paramount. The first print-out time is remarkably fast, minimizing wait times and allowing users to get back to their tasks quickly.

In addition to its speed, the Toshiba 1600XP boasts exceptional print quality. With a high resolution of up to 1200 x 1200 dpi, it produces sharp, clear text and vibrant images, making it ideal for both document printing and professional presentations. The printer uses advanced laser technology, which contributes to consistent and reliable output over time.

The Toshiba 1600XP also integrates advanced scanning capabilities, allowing users to digitize documents with ease. It offers both color and monochrome scanning options, with various file formats available, including PDF and JPEG. The automatic document feeder (ADF) simplifies the scanning process by enabling batch scanning, increasing productivity for users who frequently digitize materials.

Connectivity options are a significant highlight of the Toshiba 1600XP. It comes equipped with USB and Ethernet interfaces, facilitating seamless integration into any office network. For organizations that value mobility, the printer also supports mobile printing solutions, allowing users to print directly from their smartphones or tablets using popular applications.

Energy efficiency is another important aspect of the Toshiba 1600XP. The device is designed to minimize power consumption without compromising performance. Toshiba has incorporated eco-friendly features that help businesses reduce their carbon footprint, making it a practical choice for environmentally conscious organizations.

In summary, the Toshiba 1600XP is a multifunction printer that excels in speed, print quality, and versatility. With its robust scanning capabilities, extensive connectivity options, and energy-efficient design, the 1600XP stands out as an outstanding solution for businesses looking to enhance their document management processes. Whether it's printing, scanning, or copying, the Toshiba 1600XP delivers excellent performance to meet the needs of any fast-paced office environment.