1600XP Series Installation and Operation Manual

B-13

1600XP Command Parameters Table

Cmd

Description

Brief Description

Location Map

Example

Rqd Security

By

ID

on LCD

 

 

 

 

Level to change

 

 

Tab

Block

 

 

685

Total Flt Al-

Total Faults Allowed

Settings

C&C

10

Changeable

Service

 

lowed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

686

Flt Dis Time

Fault Disable Time

Settings

C&C

10

Changeable

Service

 

 

 

 

 

 

 

 

693

Invert Rmt

Remoted Shutdown Inverted Logic

Settings

C&C

Normally Open

Nonchangeable

User

 

SDown

- Non-volatile configuration. Default from fac-

 

 

 

Changeable

Administrator

 

 

tory is Normally Open

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

694

Reset HW

Reset Hardware Fault Latch

Settings

C&C

0

Changeable

Service

 

Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

695

Restart Mode*

Restart UPS Mode

Settings

C&C

On-Line

Nonchangeable

User

 

 

- Non-volatile configuration. Default from fac-

 

 

 

Changeable

Administrator

 

 

tory is On-Line

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

696

SWMishap

Software Mishap restart mode

Settings

C&C

1

Changeable

Service

 

Mrstrt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

697

Special

(Call Factory for Further Information)

Settings

C&C

 

Changeable

Administrator

 

Purpose

 

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

701

System Op

Total System Operation Time

Settings

HIST

123 Sec

Nonchangeable

User

 

Time

- Non-volatile history record. Default from fac-

 

 

 

Nonchangeable

Administrator

 

 

tory is zero.

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

702

Inverter Op

Total Inverter Operation Time

Settings

HIST

123 Sec

Nonchangeable

User

 

Time

- Non-volatile history record. Default from fac-

 

 

 

Nonchangeable

Administrator

 

 

tory is zero.

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

703

Backup Op

Total Backup Operation Time

Settings

HIST

123 Sec

Nonchangeable

User

 

Time

- Non-volatile history record. Default from fac-

 

 

 

Nonchangeable

Administrator

 

 

tory is zero.

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

704

UPS Lifetime

UPS Lifetime Remaining Time

Settings

HIST

61320 Hr

Nonchangeable

User

 

 

- Non-volatile history record. Default from fac-

 

 

 

Nonchangeable

Administrator

 

 

tory is 61320 Hour

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

705

Hi System

Highest System Temperature Recorded

Settings

HIST

0 C

Nonchangeable

User

 

Temp

- Non-volatile history record. Default from fac-

 

 

 

Nonchangeable

Administrator

 

 

tory is 0 C.

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

706

Hi Battery

Highest Ambient Temperature Recorded

Settings

HIST

-15

Nonchangeable

User

 

Temp

- Non-volatile history record. Default from fac-

 

 

 

Nonchangeable

Administrator

 

 

tory is -15 C.

 

 

 

Changeable

Service

 

 

 

 

 

 

 

 

Image 85
Contents 1600XP Series Page Qualified Personnel only Product Use and Warranty RestrictionsUninterruptible Power System UPS Toshiba Customer Support Center PurposeToshiba Customer Support Center Toshiba International CorporationPage Table of Contents Optional MB Maintenance Bypass Units Screen Tab SettingsPreventive Maintenance/Parts Replacement Display and KeysAppendix a 1600XP Specifications External Layouts/Dimensions/Shipping WeightsIndex Iii Page Symbols General Safety InstructionsProhibited Symbol indicates do not take action Regulatory Compliance Statement Signal WordsFCC Class a Notice EMC Directive Class a NoteCritical Fuse Sizing Equipment Warning Labels14 15 16 20 a Important Safety Instructions45 a 60 a 80 a 100 a 125 a 144 Vdc 216 Vdc 288 VdcQualified personnel shall Qualified Personnel OnlyTo be performed by Qualified Personnel Only Inspection Inspection/Storage/DisposalUnpacking StorageUPS Installation PrecautionsPage Conductor Routing and Grounding Operating PrecautionsTerminal Block UPS ConnectionsVout Output Cabling forNumber KVA 10 kVA 14-18 kVA 22 kVA Lb.-in. Nm Wire Size and Tightening TorqueUPS Model Battery Cabinet Mccb Capacity Optional Battery Cabinet ConnectionsPower Conditioning Power BackupProduct Description Application and UseStatic-Bypass Stop operation Operating ModesOn-Line Run operation EPO Emergency Power Off Function Battery Backup On batteriesBattery Low Voltage Tolerances Battery Backup Time and Discharge ProcessUPS Capacity Model Vmax Vmin Icharge Battery RechargingCommand Options Stopping the UPS Starting the UPSFront Panel Layout Display and KeysDisplay Manual Controls 1600 XP Operating Keys Monitor and Settings screensRecords screens BATLight Emitting Diodes LED Status IndicatorsEnd Input Bypass Batt History Backup System Test Faults OperationTouchscreen Menu Tree Output DC Bus Ctrl/Cfg Disp/ReyeChange Secu. Lvl Keypad ControlsShift again Write keyLogin Screen Security Passwords & Key PadRUN/Stop the UPS Screen Tab MainMimic Display Screen Tab MonitorMonitor Details Mimic Display Sample Record Screens RecordsCondition Audible Alarm FunctionsKey Cmd ID range Types of Parameters Screen Tab SettingsDISP/REYE Block No of Input Line 240V Changing UPS Parameter SettingsAccess Level Sec. Abbreviation Settings ParametersUSR ADMCalibration Screen Recalibrate the TouchscreenCommunication Interfaces MA rms Vac peak MA peak Pin Signal Function Logic UPSRemote Contacts Current Vdc peak MA peakPin Symbol Description UPS LAN Shutdown Signal Operation18.3 RS-232C 18.5 EMD RemotEye III Network CardInternal Maintenance Bypass Optional MB Maintenance Bypass UnitsLED OFF External Maintenance Bypass Battery Pack Replacement Optional Receptacle Panel Installation Instructions UPS Protection System System Protection FeaturesSystem Protection Functions Overheating Overcurrent Current Limit OverloadPreventive Maintenance Preventive Maintenance/Parts ReplacementCleaning the Touchscreen Overvoltage OvercurrentDisplay Recrd Meaning Action System Fault MessagesDisplay Record Meaning Action System Warning MessagesBtstfl BsdvBypov BypuvSystem Status Messages System Mode MessagesDisplay Meaning Display Meaning ActionPfail LansdRmtsd RO2EEERRBatt AMB Temp Average Lifetime Parts ReplacementUnit and Shipping Weights External Layouts/Dimensions/Shipping WeightsDimensional Data Electrical Conduit Knock-out DataExternal Layout for 3.6kVA and 6kVA units Snmp Port Remote Eye Slot Standard Model 3.6 10 kva Appendix a 1600XP SpecificationsUnit Capacity 6kVA 3.1 kW KVA 5.1 kW KVA 6.8 kW KVA 8.5 kW Standard Models 3.6 10 KVA CONT’D Yuasa Battery System Battery ReplacementCapacity KVA 11.9 kW1 KVA 15.3 kW1 KVA 18.7 kW1 Standard Models 14 22 kvaStandard Models 14 22 KVA CONT’D Capacity KVA 11.9 kW1 KVA 15.3 kW1 KVA 18.7 kW 1 Toshiba Part Number for 51896-FS 60995-FS Battery PackOn LCD Appendix B 1600XP Command Parameter TableTab Block ToshibaNone Toshiba H3OUT FierrChangeable Service Software compenents 251 Vref PhAdj BYP Dcov SW Dcuv SWBatt Dcub SWChrgov Stop RUNAdmin USER, AdminDvcoh ViovLansd On LCD Hist 707 Total VIUVs Total No. Of Input Undervoltage Settings 721 Total Sys Total No. of System Changes Settings Begin and end the user will be required to touch On LCD Page KVA Dimensions Appendix C 1600XP Dimensions and WeightsKVA Dimensions w/ MBS KVA Dimensions 14 / 18 / 22 kVA Dimensions w/ Optional MBS Index RS232 Ascii A5 Page UPS Page Industrial Division
Related manuals
Manual 90 pages 35.4 Kb

1600XP specifications

The Toshiba 1600XP is an advanced multifunction printer that showcases Toshiba's commitment to innovation and reliability in office technology. Designed to meet the demands of modern businesses, the 1600XP integrates several features and technologies that enhance productivity while ensuring high-quality output.

One of the key characteristics of the Toshiba 1600XP is its impressive speed. Capable of printing up to 16 pages per minute, this printer is well-suited for busy work environments where efficiency is paramount. The first print-out time is remarkably fast, minimizing wait times and allowing users to get back to their tasks quickly.

In addition to its speed, the Toshiba 1600XP boasts exceptional print quality. With a high resolution of up to 1200 x 1200 dpi, it produces sharp, clear text and vibrant images, making it ideal for both document printing and professional presentations. The printer uses advanced laser technology, which contributes to consistent and reliable output over time.

The Toshiba 1600XP also integrates advanced scanning capabilities, allowing users to digitize documents with ease. It offers both color and monochrome scanning options, with various file formats available, including PDF and JPEG. The automatic document feeder (ADF) simplifies the scanning process by enabling batch scanning, increasing productivity for users who frequently digitize materials.

Connectivity options are a significant highlight of the Toshiba 1600XP. It comes equipped with USB and Ethernet interfaces, facilitating seamless integration into any office network. For organizations that value mobility, the printer also supports mobile printing solutions, allowing users to print directly from their smartphones or tablets using popular applications.

Energy efficiency is another important aspect of the Toshiba 1600XP. The device is designed to minimize power consumption without compromising performance. Toshiba has incorporated eco-friendly features that help businesses reduce their carbon footprint, making it a practical choice for environmentally conscious organizations.

In summary, the Toshiba 1600XP is a multifunction printer that excels in speed, print quality, and versatility. With its robust scanning capabilities, extensive connectivity options, and energy-efficient design, the 1600XP stands out as an outstanding solution for businesses looking to enhance their document management processes. Whether it's printing, scanning, or copying, the Toshiba 1600XP delivers excellent performance to meet the needs of any fast-paced office environment.