Surge Protective Devices

ELECTRICAL CONNECTIONS

All electrical connections should be installed by a qualified (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes.

VERIFY THAT ALL POWER CIRCUITS ARE

DE-ENERGIZED AND LOCKED OUT BEFORE MAKING

ELECTRICAL CONNECTIONS.

Voltage Ratings and Power Source Configurations

Before making connections to the unit, verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source. See the chart on page 3 for voltage rating applications with typical power source configurations.

Wire ConnectionsWith parallel connection, the size of the wiring to the SPD unit is independent of the protected circuit s ampacity. NEC Article 285-21(B) requires surge suppressor connecting conductors to be at least #14 copper or #12 aluminum. To reduce the wiring impedance to surge currents, it is recommended that the phase, neutral (if required), and ground conductors are twisted together and routed in the same raceway (conduit). Avoid any sharp bends in the conductors.

Overcurrent ProtectionThe SPD unit conducts practically no current under normal operation and only conducts very short duration transient surge currents.

NEC Considerations - The following is from the National Electric Code 2008 Edition.

NEC 285.21 Connections

NEC 285.23 Type 1 SPD s. Shall be installed in accordance with 285.35(A) and (B).

(A)Installation. Type 1 SPD s shall be installed as follows:

(1)Type 1 SPD s shall be permitted to be connected to the supply side of the service disconnect as permitted in

230.82(4) or

(2)Type 1 SPD s shall be permitted to be connected in Type 2 locations as specified in 285.24.

(B)At the service. When installed at the services, the grounding conductor of a Type 1 SPD shall be connected to one of the following:

(1)Grounded service conductor

(2)Grounded electrode conductor

(3)Grounding electrode for service

(4)Equipment grounding terminal in the service equipment

Voltage Protection RatingsTo obtain the voltage protection ratings (VPR s), as obtained by Underwriters Laboratory, Incorporated, in accordance with the Standard for Safety, Surge Protective Devices (SPD s), Standard 1449, Third Edition, released (2009), marked on this product, the wire size listed for each product must be utilized to connect the unit to your facilities power grid. Connections made with conductors other than the wire size listed may result in different VPR s.

Circuit Ampacity Limitations Representative samples of these products have been investigated by Underwriters Laboratories, Incorporated to withstand, without exposing live circuits or components at system voltages and fault currents up to 200,000 AIC, as described in the Standard for Safety, Surge Protective Devices (SPD s), Standard 1449, Third Edition, released (2009).

System Grounding and BondingThe performance and safety of any SPD system is dependent on proper grounding and bonding. Grounding is required for safety. Correct implementation also enhances equipment performance. Incorrect grounding can reduce or impede the SPD s operation.

All electrical circuits to the SPD must include an equipment-

grounding conductor as required by the NEC and local codes.

UNGROUNDED POWER SYSTEMS ARE INHERENTLY UNSTABLE AND CAN PRODUCE EXCESSIVELY HIGH LINE-TO- GROUND VOLTAGES DURING CERTAIN FAULT CONDITIONS. DURING THESE FAULT CONDITIONS ANY ELECTRICAL EQUIPMENT, INCLUDING AN SPD, MAY BE SUBJECTED TO VOLTAGES WHICH EXCEED THEIR DESIGNED RATINGS. THIS INFORMATION IS BEING PROVIDED TO THE USER SO THAT AN INFORMED DECISION CAN BE MADE BEFORE INSTALLING ANY ELECTRICAL EQUIPMENT ON AN UNGROUNDED POWER SYSTEM. CONTACT FACTORY FOR UNGROUNDED APPLICATIONS.

An insulated grounding conductor is required in addition to any metallic raceway, which may be used as a grounding conductor. For parallel-connected SPDs, the grounding conductor should be the same wire size as the associated power conductors.

Installation, Operation and Maintenance Manual

4

IO-70103 Rev 0, 1/2013

Image 5
Contents Series Surge Protective Devices Location Considerations Unpacking and InstallationUnpacking and Preliminary Inspection Handling ConsiderationsModel # Electrical Connections Voltage Ratings and Power Source ConfigurationsNeutral Connection Parallel ConnectionsInstallation Instructions Nema 12 Metal Enclosure Option Nema 1 Panelboard Extension Enclosure Option Troubleshooting SERVICING/ Maintenance Monitoring FeaturesTroubleshooting Corrective Maintenance The Emerson Network PowerSurge Protective Devices Emerson Network Power

510 specifications

The Emerson 510 is a cutting-edge, versatile automation controller designed to enhance operational efficiency, improve productivity, and ensure seamless management across various industries. Known for its robust architecture, the Emerson 510 integrates a host of features and technologies that cater to the demands of modern automation processes.

One of the standout characteristics of the Emerson 510 is its modular design, which allows users to customize their systems according to specific application requirements. This flexibility ensures that businesses can scale their operations without having to invest in entirely new systems. The controller supports a variety of I/O modules, communication cards, and power supplies, making it suitable for a wide range of industrial applications, from manufacturing to processing plants.

The Emerson 510 is powered by advanced technologies that promote faster data processing and enhanced connectivity. It features an intuitive user interface that simplifies programming and monitoring, allowing operators to interact with the system effortlessly. The controller also supports various programming languages, including Ladder Logic and Structured Text, catering to the preferences of different users and ensuring that system integration is as smooth as possible.

Another significant advantage of the Emerson 510 is its real-time data acquisition and processing capabilities. This functionality enables operators to monitor system performance, receive alerts, and make data-driven decisions to optimize operations. The controller’s networking capabilities allow for seamless integration into larger control systems, facilitating communication with other devices and systems, such as SCADA and HMI platforms.

Security is a critical aspect of modern industrial control systems, and the Emerson 510 addresses this concern with robust cybersecurity features. It incorporates advanced encryption protocols, user authentication, and access controls to ensure that the system remains protected against potential threats and vulnerabilities.

In conclusion, the Emerson 510 automation controller stands out in the industry with its modular design, advanced processing capabilities, user-friendly interface, and strong security features. It empowers businesses to enhance operational efficiency, streamline processes, and drive innovation, making it an invaluable asset for any organization looking to thrive in an increasingly competitive landscape.