Liebert LM, Type SS, SAD Hybrid Advantage, AccuVar Liebert Active Tracking Filter Series Type F

Page 12

Surge Suppression Systems

Liebert Active Tracking Filter Series — Type F

Surge Protective Device (SPD)

Installation Instructions

1.Ampacity: The filter’s maximum continuous current (Ampere) rating must be greater than or equal to the protected load’s full load amps or overcurrent protection (Circuit Breaker) rating.

2.Insure that all power is removed before beginning installation. A qualified licensed electrician shall install all electrical connections.

3.The SPD is provided in a NEMA 3R, NEMA 4, NEMA 4X or NEMA 12 enclosure. The SPD is suitable for use in indoor (NEMA 12) or outdoor (NEMA 3R, 4, 4X) installations.

4.Determine where the SPD is to be mounted. Punch or cut proper hole size in the side of the SPD closest to the knockout to be utilized in the service panel. Wall Mounted Units: Drill mounting holes in wall at location picked for SPD next to service panel using mounting dimension from the tables on page 17. Mount surge suppressor using 3/8-16 hardware or equivalent.

5.Units up to 225 amps are suitable for short circuit current ratings up to 25,000 amps. For short circuit currents up to 50,000 amps, Class RK5 fuses sized up to 125% of the filter’s continuous current rating are required. Units rated at 400 to 800 amps are suitable for available symmetrical short circuit currents up to 50,000 amps. For short circuit currents up to 100,000 amps, Class L Fuses sized up to 125% of the filter’s continuous current rating are required. Units 1200 amps and above are suitable for available symmetrical short circuit currents up to 200,000 amps.

6.For best performance, keep input and output wiring separated as much as practical to eliminate input-to-output coupling of noise and transients. Do not route input and output wiring in the same raceway. If practical, terminate input and output raceways (conduits) at opposite ends of the active tracking filter enclosure (input near the top and output near the bottom).

7.The Liebert Active Tracking Filter System is wired in-line (in series) with the protected load(s). See Figures on the following page.

8.Terminals are provided inside the Liebert Active Tracking Filter System for the line (phase), neutral (if used), transient ground, and equipment safety ground connections. See page 11 for terminal wire size ranges.

9.Connect black wires (line or phase) marked L1/A, L2/B or L3/C, the white wire (neutral) marked N, and the green wire (ground) marked G, of the SPD using the wire range listed in the table on page 12 in accordance with the National Electric Code (NEC) Article 285 and all local codes. To yield the best performance of the SPD within the electrical distribution system, avoid sharp bends.

10.Connection to the Form ‘C’ contacts shall be with #18 – 22 AWG. Contacts are rated 5 amps at 250 VAC maximum with a power factor of 1.0.

11.Apply power. The surge protector is fully operational when the GREEN LEDs on the modules and the front door of enclosure are illuminated. If the GREEN LEDs are extinguished or the RED LED is illuminated, check to ensure that power is applied to the SPD. If an abnormal indication is present, remove power to the SPD and contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.

12.Periodically monitor the status of the LEDs. Reduced protection exists if the GREEN LEDs are extinguished or the RED LED is illuminated. Please contact Liebert/Emerson Network Power Surge Protection at 1-800-288-6169 or 1-607-724-2484.

13.The protection modules in these SPDs are replaceable, contact Liebert/Emerson Network Power Surge Protection for replacement.

Installation, Operation and Maintenance Manual

10

Liebert TVSS Units SL-22085 Rev 2, 11/2006

Image 12
Contents Interceptor II, SAD Hybrid Advantage, Type SS, LM, AccuVar Page Surge Suppression Systems Unpacking and Preliminary Inspection Handling ConsiderationsStorage Location ConsiderationsVoltage Ratings and Power Source Configurations Electrical ConnectionsVoltage Ratings and Power Source Configurations Source ConfigurationsTypical Parallel Connections with Internal Rotary Disconnect System Grounding and Bonding Troubleshooting / Servicing / Maintenance Troubleshooting Preventative Maintenance Inspection and Cleaning ServicingInstallation Instructions Surge Suppression SystemsType LM Series AccuVar SeriesPowerSure LPL Allowable RangeSeries Surge Protective Device SPD Installation Instructions Liebert Active Tracking Filter Series Type FLiebert Active Tracking Filter System GroundLiebert PanelGuard Series Type Lpge SPD Interconnect Assembly Installation Instructions Liebert AccuGuide Series Type ACGNational Electrical Code NEC Considerations Connection ConduitConduit Size Equipment PerformanceDimensional Information Alarm Enable/Disable Feature Audible Alarm AccuVar SeriesHybrid Advantage Series Type H AccuVar Series Type ACV & AIIModel Dimensions Inches Active Tracking Filter Series Type FModel Application Wire Range Type SS SeriesBreaker Size Unit Dimensions Inches Wire Size BreakerType LM Series LbsPowerSure Medium Exposure Series Type LPM 375750 000 500 000PowerSure Low Exposure Series Type LPL PanelGuard Series Type Lpge Example Installations Surge Suppression Systems Limited Warranty Items Not Covered By Warranty LimitationsMiscellaneous Surge Suppression Systems Items Not Covered By Warranty Liebert Corporation