Surge Suppression Systems
E | F | (4X) |
|
A
D
Type LM Series
Service Panel for
Loads to be Protected
Dedicated
CDisconnect
(Optional)
Recommended Wire
Entrance
Phase L1/A
Phase L2/B
Phase L3/C
Disconnect/Main
Breaker for
Panel
Neutral Buss
Ground Buss
B |
1.840
Max.
|
|
|
|
|
| LM Series |
|
|
| ||
Unit |
| Dimensions (Inches) |
| Weight | Suggested | Suggested | Allowable | Allowable | |||
A | B | C | D | E | F | (lbs) | Breaker Size | Wire Size | Breaker | Wire Range | |
| (AWG) | Range | |||||||||
|
|
|
| ||||||||
LM060 | 16 | 14 | 8 | 16.75 | 12 | 0.31 | 32 | 40 A | #8 |
|
|
LM080 |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |
LM100 |
| 14 | 8 | 16.75 | 12 | 0.31 | 41 | 40 A | #8 | 15A | #14 – #2 |
LM125 | 16 | ||||||||||
LM150 |
|
|
|
|
|
|
|
|
|
|
|
LM200 |
| 16 | 9 | 21.25 | 10 | 0.44 | 56 | 100 A | #2 |
|
|
LM225 | 20 |
|
| ||||||||
LM250 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LM Series, with Rotary Disconnect |
|
|
| ||||||
| Unit |
| Dimensions (Inches) |
| Weight | Suggested | Suggested | Allowable | Allowable |
| |||
| A | B | C | D | E | F | (lbs) | Breaker Size | Wire Size | Breaker | Wire Range |
| |
|
| (AWG) | Range |
| |||||||||
|
|
|
|
|
| ||||||||
| LM060 | 16 | 14 | 8 | 16.75 | 12 | 0.31 | 32 | 40 A | #8 | 15A | #14 – 1/O |
|
| LM080 |
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
| LM100 |
| 14 | 8 | 16.75 | 12 | 0.31 | 41 | 40 A | #8 | 15A |
|
|
| LM125 | 16 | #14 – 2/O |
| |||||||||
| LM150 |
|
|
|
|
|
|
|
|
|
|
|
|
| LM200 |
| 16 | 9 | 21.25 | 10 | 0.44 | 56 | 100 A | #2 | 15A | #14 – 2/O |
|
| LM225 | 20 |
| ||||||||||
| LM250 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Installation, Operation and Maintenance Manual |
|
| 19 |
| Liebert TVSS Units |