Converters. From the Converters
Converter Parameters | Description |
|
|
1- High Voltage | If converter voltage exceeds this value, a converter high |
Threshold (V) | voltage alarm occurs. To set the alarm action, see Converter |
| Alarms. |
|
|
2- Low Voltage | If converter voltage drops below this value, a converter low |
Threshold (V) | voltage alarm occurs. To set the alarm action, see Converter |
| Alarms. |
|
|
3- Fail Safe (V) | The value sent to the converter controllers to use if |
| communication is lost with the master controller or if the |
| master controller board fails. |
|
|
4- Set Point (V) | The initial set point used in the voltage control loop. |
|
|
5- Fail Max (V) | The value sent to the converter controllers to define the |
| maximum set point allowed (the converter fail maximum |
| limit). |
|
|
6- Fail Min (V) | The value sent to the converter controllers to define the |
| minimum set point allowed (the converter fail minimum |
| limit). |
|
|
7- Communications Fail | The time in seconds (60 by default) that a converter waits |
(sec) | for communication with the master controller before |
| resetting all its values to their defaults. |
|
|
8- Accept Changes | Use this option to save your changes. |
|
|