ADC HRM-238 L1 user manual Identifying Alarms, Turning UP the System, Insert Fuse

Page 19

LTPH-UM-1237-04

Installation

 

 

IDENTIFYING ALARMS

Alarm relay contacts for each management unit are on J13 and J14 (Figure 11). Install wiring between these pins and an alarm monitoring device per local practice. Table 7 describes the alarm J13 and J14 pinouts.

H0651-A

Alarm relay pins (J14)

 

 

Alarm relay pins (J13)

 

 

Figure 11. Alarm Relay Wire-Wrap Pins

 

 

Table 7. Alarm J13 and J14 Pinouts

 

 

 

 

 

 

 

Pin

Description

Pin

Description

 

 

 

 

 

 

1

CRIT_AUD_NC_A

13

MIN_AUD_NC_A

 

 

 

 

 

 

2

CRIT_AUD_COM_A

14

MIN_AUD_COM_A

 

 

 

 

 

 

3

CRIT_AUD_NO_A

15

MIN_AUD_NO_A

 

 

 

 

 

 

4

CRIT_VIS_NC_A

16

MIN_VIS_NC_A

 

 

 

 

 

 

5

CRIT_VIS_COM_A

17

MIN_VIS_COM_A

 

 

 

 

 

 

6

CRIT_VIS_NC_A

18

MIN_VIS_NO_A

 

 

 

 

 

 

7

MAJ_AUD_NC_A

19

SYS_ID_NC_A

 

 

 

 

 

 

8

MAJ_AUD_COM_A

20

SYS_ID_COM_A

 

 

 

 

 

 

9

MAJ_AUD_NO_A

21

SYS_ID_NO_A

 

 

 

 

 

 

10

MAJ_VIS_NC_A

22

EXT_ACO_A

 

 

 

 

 

 

11

MAJ_VIS_COM_A

23

LGND

 

 

 

 

 

 

12

MAJ_VIS_NO_A

 

 

 

 

 

 

 

 

 

TURNING UP THE SYSTEM

Perform the following procedures prior to installing the management unit(s) into the shelf.

Insert Fuse

Insert an appropriately sized fuse(s) into the equipment bay fuse panel for the circuit(s) where the HRM-238 shelf battery wire(s) were terminated. Refer to the appropriate management unit user manual for power consumption, power dissipation, and current drain.

HRM-238 List 1

July 21, 2004

11

Image 19
Contents Clei T1MFW004 HRM-238 List 1 HiGain Retrofit Management ShelfRevision History Inspecting Shipment Using this ManualInspecting Shipment Table of Contents List of Figures List of Tables OS Port P2 and P4 Alarm J13 and J14 PinoutsList of Tables Overview FeaturesApplication Operational CapabilitiesRecommended Network Setup for 3190 Type Shelves Management Cabling Connector Purpose Type Gender No. PinsInspecting Your Shipment InstallationInstalling the HRM-238 Shelf Installing Frame Ground and Battery PowerTerminal Block TB1 Installing Communication WiringFor 220 type mechanics Connect NMA WiringP1 and P6 NMA Connectors Connect to a Computer, Terminal, or Modem Connect to a LAN or Interconnect ShelvesAUX P3 and P5 Connectors Turning UP the System Identifying AlarmsInsert Fuse Verify Cabling Installing the Management UnitsSecure Cabling Physical Appendix a SpecificationsAppendix B Product Support Appendix C Abbreviations Appendix C Abbreviations FCC Compliance Certification and WarrantyTechnical Assistance World Headquarters