Siemens siemens compact universal controllers manual Technical data, Storage, Transport, Operation

Page 4

Technical data

General controller data

Mains voltage

AC 110...240 V +10 % / -10 %

 

 

Mains frequency

48...63 Hz

 

 

Safety class

II to DIN 0631

 

 

Mounting position

optional

 

 

Terminals for

2 x 1.5 mm² or 1 x 2.5 mm²

 

 

Power consumption

max. 10 VA

 

 

Safety extra low-voltage

DC 24 V

 

 

Contact rating of the control outputs

 

 

 

 

(relays «K1...K3»)

2 A / AC 24...240 V

 

 

- Up to 2 x 105 switching cycles

 

 

- Up to 107 switching cycles

0.1 A / AC 24...240 V

 

 

Weight complete with housing

approx. 760 g

 

 

Recommended actuator running time

15...60 s

 

 

Degree of protection of housing

 

 

 

-

Front

IP 65, EN 60529

 

 

-

Base

IP 20, EN 60529

Environmental

 

 

Storage

DIN EN 60 721-3-1

conditions

Temperature range

-20...+60 °C

 

 

Humidity

< 75 % r.h.

 

 

Transport

 

 

 

Temperature range

-40...+70 °C

 

 

Humidity

< 75 % r.h.

 

 

Operation

 

 

 

Temperature range

-20...+50 °C

 

 

Humidity

< 75 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

4/10

Building Technologies

CC1N7865en

HVAC Products

01.09.2005

Image 4
Contents 7865 Installation notes Service notesMounting notes Commissioning notesType summary Controller with Packaging variants 20 pieces, without documentationAdapter frame for replacing the RWF32 BracketTechnical data StorageTransport OperationRWF40 FunctionFunction of the controller when used for burner control Measurement range Or 3-wire resistance Pt100 / IEC Connection diagram basic diagram RWF40Dimensions Dimensions cont´d ARG41