Function of the controller when used for burner control

Low-fire operation

In low-fire operation, the RWF40... operates like a control thermostat or pressurestat.

 

This means that it operates as a 2-position controller maintaining the required setpoint

 

by switching the burner on and off. The switching differential for 2-position operation

 

can be adjusted within a wide range. If the demand for heat increases, the controller

 

switches to high-fire operation only when an adjustable limit is exceeded. This function

 

is aimed at optimizing the burner´s switching ratio.

High-fire operation,

In that case, the RWF40... operates as a 2-position controller with adjustable switching

2-stage control

thresholds. Using the relays of the 3-position output, the RWF40... drives the actuator

 

to the 1st and 2nd output stage. In this operating mode, the optional analog output

 

switches between the minimum signal for the 1st stage and the maximum output signal

 

for the 2nd stage.

High-fire operation,

In that case, the RWF40... operates as a PID / PI controller with a 3-position output

modulating control

without position feedback signals or, optionally, with a modulating output. By making

 

use of its self-setting facility, the RWF40... is able to determine the PID / PI control

 

parameters, or the parameters can be set manually.

Binary input 1 (change- over of operating mode)

Binary input 2 (setpoint shifting or setpoint changeover)

Limit comparator

Operation

Weather-dependent setpoint shifting

Using a potential-free contact, the RWF40... can be switched from the modulating mode to 2-stage operation.

In the case «setpoint shifting» is configured, the current setpoint is shifted by an adjust- able amount. Configuration of «setpoint changeover» provides changeover between 2 setpoints adjusted on the RWF40... If analog input 2 is configured for an «external set- point», changeover is provided between the setpoint adjusted on the RWF40... and an external setpoint.

Potential-free contact «K6» can be assigned a number of functions. Example: Limit value supervision

4 buttons on the unit front are used to operate and program the RWF40... During op- eration and programming, the 7-segment displays show the parameter values and pa- rameter names.

The controller´s standard configuration ex works is such that when connecting a QAC22… outside sensor, automatic changeover to weather-dependent setpoint shifting takes place.

The signal delivered by the QAC2... outside sensor must not be fed parallel to sev- eral RWF40...!

6/10

Building Technologies

CC1N7865en

HVAC Products

01.09.2005

Image 6
Contents 7865 Mounting notes Installation notesService notes Commissioning notesAdapter frame for replacing the RWF32 Type summary Controller withPackaging variants 20 pieces, without documentation BracketTransport Technical dataStorage OperationRWF40 FunctionFunction of the controller when used for burner control Measurement range Or 3-wire resistance Pt100 / IEC Connection diagram basic diagram RWF40Dimensions Dimensions cont´d ARG41