Siemens siemens compact universal controllers manual RWF40, Function

Page 5

Function

The RWF40... provides the following functions:

-One digital PID controller with a 3-position or analog output (optional)

-To control 2-stage burners, the RWF40... can be switched over to provide 2- position control

-Automatic thermostat (or pressurestat) function in low-fire operation

-One shift controller for weather-dependent setpoint shifting

-One minimum limiter and one maximum limiter for the boiler temperature or the boiler pressure

-One limit thermostat to DIN 3440 (output 1)

-One potential-free configurable contact

-Manual operating mode

-Communication via serial port (option)

-Self-setting function

Block structure

3 analog inputs

 

Input 1:

 

Actual value

 

for Pt100, Ni100, Pt1000,

 

LG-Ni1000,

 

thermocouples

 

or standard signals

 

Input 2:

 

External setpoint,

 

setpoint shifting

 

for 0...1 kresistor

 

or linearized

 

standard signals

 

Input 3:

 

Outside temperature

 

for Pt1000, LG-Ni1000

 

2 binary inputs

 

For potential-free

 

contacts

 

Input 1:

 

Operating mode changeover

 

Input 2:

 

Setpoint shifting /

 

changeover

 

Power supply

 

AC 110 ...240 V +10%/-10%,

 

48...63 Hz, max. 10 VA

 

7865f01e/0905

RWF40...

Release of burner

Output 1:

- Relay (N.O. contact)

Floating output

Output 2:

-Relay (actuating device open)

Output 3:

- Relay (actuating device closed)

Limit comparator

Output 4:

- Relay (N.O. contact)

Power supply measuring transducer

DC 24 V, 30 mA (short-circuit proof)

Analog output (optional)

Output 5:

Analog output

DC 0...10 V, DC 0...20 mA,

DC 4...20 mA

Serial port (optional)

RS-485

MOD bus protocol

 

5/10

 

 

Building Technologies

CC1N7865en

HVAC Products

01.09.2005

Image 5
Contents 7865 Service notes Installation notesMounting notes Commissioning notesPackaging variants 20 pieces, without documentation Type summary Controller withAdapter frame for replacing the RWF32 BracketStorage Technical dataTransport OperationFunction RWF40Function of the controller when used for burner control Measurement range Or 3-wire resistance Pt100 / IEC RWF40 Connection diagram basic diagramDimensions ARG41 Dimensions cont´d