Omega IP710 SERIES manual Pneumatic Connections, Electrical Connections

Page 7

Figure 3 - DIN 43650 Connector

3.90

1.40

3.08

1.29

1.4 Pneumatic Connections

DIN Rail mounting kit IP610-DM

.61

15.5

1.68

42.7

DIN Rail Kit suitable for EN-50035, EN-50045 and EN-50022 Rails

1.4.1Clean all pipe lines to remove dirt and scale before installation.

1.4.2Supply air must be filtered to 40 microns and free of moisture and lubricants.

1.4.3The 1/4” NPT inlet and outlet connections are labeled on the body. Plug all unused ports with pipe plugs supplied with the unit. Avoid getting pipe sealant inside the piping or transducer.

1.5Electrical Connections

1.5.1Conduit Connection (current to pressure) Electrical connections are made to the red (+) and black (-) leads. The green lead is furnished for case ground (see figure 4).

Figure 4

I/P Conduit Connection

Green Lead (Ground)

Red Lead (+)

Black Lead (-)

Figure 5 - DIN 43650 Connector

1

2

3

Terminal

I/P Connection

1Positive (+)

2Negative (-)

3Unused

Ground (+)

Figure 6 - I/P Conduit Connection

Page 4

Image 7
Contents User’s Guide Servicing North America WARRANTY/DISCLAIMER Contents Physical Specifications SpecificationsFunctional Specifications Performance SpecificationsPrinciple of Operation DescriptionMounting Electrical Connections Pneumatic ConnectionsIntrinsically Safe Suitable for Calibration OperationDirect Acting Calibration Split Range Reverse Acting CalibrationPrecautions Maintenance and RepairsTroubleshooting CleaningTemperature