Omega IP710 SERIES manual Operation, Direct Acting Calibration

Page 9

2. OPERATION

2.1Calibration

2.1.1All units are shipped from the factory calibrated, direct acting.

2.1.2If the user requires a different mode of operation (i.e. reverse acting, split range) it is necessary to reposition inter- nal electrical switches as indicated below. Though the units are factory calibrated for direct acting it is suggested that the user check the calibration.

2.1.3It is not necessary to remove the cover of the unit for calibration if the direct acting mode is desired.

2.2Direct Acting Calibration

2.2.1In direct acting operation the unit is calibrated so that minimum input signal corresponds to minimum output pressure and increasing input signal results in increasing output pressure.

2.2.2Apply the minimum input signal of the range being used (e.g. 4mA for a 4-20mA unit) (see figure 6).

2.2.3Observe the output pressure. If necessary, adjust the zero screw until reaching minimum output pressure setting. Turn zero screw clockwise to decrease and counter clockwise to increase.

2.2.4Apply the maximum input signal of the range being used (e.g. 20mA for a 4-20mA unit).

2.2.5Observe the output pressure. If necessary, adjust the span screw until reaching maximum output pressure setting. Turn span screw clockwise to decrease and counter clockwise to increase.

2.2.6After setting the span it will be necessary to recheck the zero. Repeat steps 1-4 until both end points are at required values.

Figure 6 - Zero Adjustment and Span Adjustment

Zero Adjustment

 

 

 

 

 

 

 

 

 

 

 

 

Span Adjustment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 7 - Direct Acting - Position of switches for forward acting operation (all output ranges).

Standard setting as supplied by factory.

Signal

4-20 mA

Page 6

Image 9
Contents User’s Guide Servicing North America WARRANTY/DISCLAIMER Contents Functional Specifications SpecificationsPerformance Specifications Physical Specifications Description Principle of Operation Mounting Electrical Connections Pneumatic ConnectionsIntrinsically Safe Suitable for Operation CalibrationDirect Acting Calibration Split Range Reverse Acting CalibrationTroubleshooting Maintenance and RepairsCleaning PrecautionsTemperature