Tumblers – 120 and 170

3

2

1

4

5TMB2103N

TMB2103N

1Removable strip of panel in framing wall to permit removal of tumbler from framing wall

2Partition or bulkhead

3Minimum distance between exhaust opening and roof, ground or other obstruction: 36 in. (914 mm)

42 in. (51 mm) minimum clearance on both sides of duct

5Exhaust airflow – maximum length of duct: 14 ft. (4.3 m)

Figure 2

NOTE: Do not install wire mesh or screen in exhaust duct opening to avoid lint build-up or impacting proper discharge of air from tumblers.

NOTE: Where exhaust duct pierces a combustible wall or ceiling, the opening must be sized per local codes.

NOTE: Inside of duct must be smooth. Do not use sheet metal screws to join sections.

Consult your local building code for regulations which may also apply.

13

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

3-09-71

Image 14
Contents On-Premise Laundry Planning Handbook Contents Gas Steam/Thermal Oil Pound IntroductionModel Identification Tumblers 120 Conversion Table Multiply To ObtainGas Models Specifications and DimensionsSpecifications Pound Steam ModelsExhaust Outlet Dimensions and Locations Models 120L/N Pound Tumbler Dimensions and Exhaust Outlet LocationsCabinet Dimensions Models 120L/N 120SExhaust Outlet Dimensions and Locations Models 170L/N/S Pound Tumbler Dimensions Exhaust Outlet LocationsCabinet Dimensions Models 170L/N/S 170L/N Electric and Gas Connection Locations for Gas ModelsModels Electrical Connection Gas Connection Models Electrical Connection Electric and Steam Connection Locations for Steam Models170S Installation Pre-Installation InspectionTumbler Enclosure Make-Up Air Exhaust RequirementsLayout VentingIndividual Venting Duct Equivalent Length Diameter Rigid Straight DuctTMB2103N Manifold Venting Duct Pound Mm DuctDuct Pound Station Mm Duct TWO Manifold AssembliesElectrical Requirements