IPSO TMB1268C installation manual Electrical Requirements

Page 18

Tumblers – 120 and 170

Electrical Requirements

Refer to Table 5.

NOTE: Minimum wire sizes are obtained from Canadian Electrical Code and are intended for use as a guideline only. Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.

NOTE: Electrical specifications below are subject to change without notice. Always refer to product

serial plate for most current specifications of product being installed.

NOTE: Use copper conductors only.

NOTE: 3 Phase Only– Each tumbler must be connected to its own individual branch circuit breaker, not fuses, to avoid the possibility of “single phasing” and causing premature failure of the motor(s).

For 120 Pound Tumbler Models

Serial Plate Rating

Terminal Block

Rated

Breaker

Breaker

Recommended

Connections Required

Current*

Rating

Poles

Wire Size

 

 

 

 

 

 

 

208-230V/60Hz/3ph

L1, L2, L3 and ground

7.7

15 Amps

3

14 AWG (2.08 mm2)

380-415V/50Hz/3ph

L1, L2, L3 and ground

3.8

10 Amps

3

14 AWG (2.08 mm2)

380V/60Hz/3ph

L1, L2, L3 and ground

4.1

10 Amps

3

14 AWG (2.08 mm2)

440V/60Hz/3ph

L1, L2, L3 and ground

3.8

10 Amps

3

14 AWG (2.08 mm2)

460-480V/60Hz/3ph

L1, L2, L3 and ground

3.9

10 Amps

3

14 AWG (2.08 mm2)

* Current ratings vary slightly depending on model; refer to serial plate.

For 170 Pound Tumbler Models

Serial Plate Rating

Terminal Block

Rated

Breaker

Breaker

Recommended

Connections Required

Current*

Rating

Poles

Wire Size

 

 

 

 

 

 

 

208-230V/60Hz/3ph

L1, L2, L3 and ground

13.5

20 Amps

3

12 AWG (3.31 mm2)

380-415V/50Hz/3ph

L1, L2, L3 and ground

6.9

15 Amps

3

14 AWG (2.08 mm2)

380V/60Hz/3ph

L1, L2, L3 and ground

6.6

15 Amps

3

14 AWG (2.08 mm2)

440V/60Hz/3ph

L1, L2, L3 and ground

6.4

15 Amps

3

14 AWG (2.08 mm2)

460-480V/60Hz/3ph

L1, L2, L3 and ground

6.7

15 Amps

3

14 AWG (2.08 mm2)

* Current ratings vary slightly depending on model; refer to serial plate.

Table 5

17

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

3-09-71

Image 18
Contents On-Premise Laundry Planning Handbook Contents Introduction Model IdentificationGas Steam/Thermal Oil Pound Tumblers 120 Conversion Table Multiply To ObtainGas Models Specifications and DimensionsSpecifications Pound Steam ModelsExhaust Outlet Dimensions and Locations Models 120L/N Pound Tumbler Dimensions and Exhaust Outlet LocationsCabinet Dimensions Models 120L/N 120SPound Tumbler Dimensions Exhaust Outlet Locations Cabinet Dimensions Models 170L/N/SExhaust Outlet Dimensions and Locations Models 170L/N/S Electric and Gas Connection Locations for Gas Models Models Electrical Connection Gas Connection170L/N Electric and Steam Connection Locations for Steam Models 170SModels Electrical Connection Installation Pre-Installation InspectionTumbler Enclosure Make-Up Air Exhaust RequirementsLayout VentingIndividual Venting Duct Equivalent Length Diameter Rigid Straight DuctTMB2103N Manifold Venting Duct Pound Mm DuctDuct Pound Station Mm Duct TWO Manifold AssembliesElectrical Requirements