Fisher & Paykel DGGX1US installation instructions Determine vent duct length

Page 10

To reduce condensation, insulate any ducting which passes through unheated areas.

Slope the duct gently downwards to the hood, to drain condensation and reduce lint build up. Avoid sag or loops in the duct as they may collect and store water and accumulate lint.

Before using an existing exhaust duct system for a dryer ensure that:

No plastic or other potentially combustible duct or flexible metal foil ducting has been used.

The duct is not pierced, kinked or crushed.

The duct does not exceed the maximum recommended length for the new dryer.

The exhaust hood damper opens and closes freely and with sufficient movement.

Static pressure in the exhaust ducting does not exceed 1 inch (250Pa), or is not less than 0 inches of water column (ie. negative pressure), when measured with a manometer in the first 6 inches of the duct, with the dryer running on Air Dry (no heat) setting.

The exhaust duct system meets all relevant local, state and national codes.

All ducting should be inspected and cleaned at least once a year to remove accumulated lint. Frequently check that the damper on the exhaust hood moves sufficiently and opens and shuts freely.

Mobile home installations

A Mobile Home Installation Kit is available (see Accessories page 4 and notes page 8).

Determine vent duct length

This dryer can only be vented from the rear and must be exhausted to the outdoors.

Different types of vent arrangements are shown below.

10

Image 10
Contents Installation instructions DGGX1USWhat to do if you smell gas Important safety instructions Tools required Read this before you start installing your dryerAccessories Parts suppliedLocation requirements To the installerExplosion Hazard Alcove or closet installation Lid clearance DimensionsExhaust outlet location Mobile home installation Exhausting Fire HazardDetermine vent duct length Maximum length of exhaust duct Preferred 4 Hoods Alternative installation for close clearances Exhaust venting Unpacking InstallationExcess Weight Hazard Remove packagingFitting the front feet Electrical Shock Hazard Electrical requirementsGrounding instructions Natural Gas Gas requirementsGas type LP Gas conversionConnecting to the gas supply Connecting gas to your dryerGas ignition Connecting to the dryer Completing the connectionFinal installation check list Level machinePage Page Installation Instructions Published 03/2004 Part No a