SYMPTOMS | PROBABLE CAUSE | REMEDY |
|
|
|
Dryer not running. | a. Disconnect open. | a. Close disconnect. |
High temperature light off, |
|
|
analyzer gauge normal. | b. Fuse blown. | b. Replace fuse. |
|
|
|
| c. Wiring, improper or broken. | c. Check wiring diagram or |
|
| repair. |
|
|
|
| d. Control transformer | d. Replace. |
| defective. |
|
|
|
|
| e. Unit not turned on. | e. Turn unit on. |
Dryer not running. | a. Overload tripped. | a. Allow to cool and reset. |
High temperature light on, |
| Check for overload. |
analyzer gauge normal. |
|
|
| b. High pressure switch open | b. Reset and check for cause. |
| (if supplied). |
|
|
|
|
| c. Low water pressure | c. Increase water pressure. |
| (water cooled). |
|
|
|
|
| d. Low oil pressure switch | d. Reset and check oil level. |
| (if supplied). |
|
|
|
|
| e. High suction gas | e. Check for high ambient or |
| temperature. | overloaded condition. |
|
|
|
|
|
|
Dryer running. | a. High inlet temperature. | a. Check aftercooler. |
Analyzer gauge high. |
|
|
| b. High ambient | b. Cool ambient or relocate |
| temperature. | unit. |
|
|
|
| c. Dirty or plugged | c. Clean condenser coil. |
| condenser coil. | Blow with compressed air. |
|
|
|
| d. Defective water regulator | d. Repair or replace. |
| (water cooled). |
|
|
|
|
| e. Defective fan control. | e. Replace. |
|
|
|
| f. Defective fan motor. | f. Replace. |
TROUBLESHOOTING GUIDE continued