AT&T D-10,000, D-320 operating instructions Water downstream, Dryer

Page 12

SYMPTOMS

PROBABLE CAUSE

REMEDY

 

 

 

 

g. Defective refrigerant

g. Repair or replace

 

compressor valves.

compressor.

 

 

 

 

h. Suction pressure too high.

h. Adjust hot gas bypass

 

 

valve.

 

 

 

 

 

 

Dryer running.

a. Leaky refrigerant circuitry.

a. Locate and repair.

High temperature light on,

 

 

analyzer gauge pressure low.

b. Suction pressure too low

b. Adjust hot gas

 

Check refrigerant charge.

bypass valve.

 

 

 

 

 

 

Dryer running.

a. Defective hot gas bypass

a. Replace.

High temperature light off,

valve.

 

analyzer gauge pressure low.

 

 

 

b. Defective fan control

b. Replace.

 

(low ambient control).

 

 

 

 

 

c. Low ambient temperature.

c. Heat ambient or relocate

 

 

dryer.

 

 

 

 

d. Low refrigerant charge.

d. Repair leak and add

 

 

refrigerant.

 

 

 

 

 

 

Dryer not running.

a. Low pressure switch open.

a. Check for leak and repair.

High temperature light on,

 

 

analyzer gauge pressure low.

b. Service valves closed.

b. Open valves.

 

 

 

 

c. High suction gas

c. Check for leak.

 

temperature.

 

 

 

 

 

 

 

Water downstream of

a. Trap not functioning.

a. Clean or repair trap.

the dryer.

 

 

 

b. High inlet temperature.

b. Check aftercooler.

 

 

 

 

c. Excess flow.

c. Dryer undersized.

 

 

Replace with larger dryer.

 

 

 

 

d. Low air pressure.

d. Dryer undersized.

 

 

Replace with larger dryer.

 

 

 

 

e. Bypass valve open.

e. Close valve.

TROUBLESHOOTING GUIDE continued

SYMPTOMS

PROBABLE CAUSE

REMEDY

12

Image 12
Contents Operating Instructions 107 W. Main Street Worthington, PA Phone 724.297.3416 FaxContents Introduction ReceivingLocation FoundationElectrical Compressed AIR Circuit Refrigerant CircuitLow Pressure Switch High Pressure SwitchCrankcase Heater Where Required Expansion ValvesWater Pressure Switch Water Cooled only High Temperature ControlStart Timer Oil SightglassSTART-UP Design Conditions SHUT-DOWNWATER-COOLED Models Cooling Water Requirements Maintenance Installation of Remote Condenser OptionalCooling Water Requirements Dryer not running Dryer runningWater downstream DryerPower light on but dryer High pressure drop acrossDryer inlet and outlet Not running