AT&T D-320 Oil Sightglass, Refrigerant Liquid Line Filter-Dryer, High Temperature Control

Page 7

10. Oil Sightglass:

The oil sightglass is found on the side of the crankcase on accessible scroll compressors to provide a visual means of checking the oil level. The oil must be checked only while the compressor is in operation. During compressor operation the oil sight glass should be approximately 1/2 full.

11.Refrigerant Liquid Line Filter-Dryer:

A liquid line filter-dryer is used on all AIR/TAK refrigerated dryers. The purpose of the filter-dryer is to eliminate the possibility of moisture, or other foreign particles, from moving throughout the system. These particles, such as carbon, can cause early compressor failure. The filter-dryer also has a high quality desiccant which is capable of removing moisture to a very low point and can also remove a reasonable quantity of acid.

12.Water Pressure Switch (Water Cooled only):

This control is used only on dryers equipped with water cooled condensers. The purpose of this switch is to assure that adequate water pressure and flow is available to the refrigerant condenser.

13.Desuperheating Valve (D-1250 and larger):

This valve is used on larger capacity dryers. Due to the larger refrigerant charges associated with these models the addition of the desuperheating valve is necessary. The valve's purpose is to provide liquid refrigerant to desuperheat hot discharge gas used to establish suction gas pressure.

14.High Temperature Control:

This control is used to protect the compressor from excessive return gas temperature. During the start-up phase, the high temperature light may be lit until the refrigeration system reaches its normal running temperatures and pressures. (See Start-up; Section I).

During normal operation on Models 320 SCFM through 2000 SCFM, this control will activate the high temperature light when return gas temperatures become excessive. Immediate action is required by the customer to turn off the dryer.

On models 2500 SCFM and above, this control will activate the high temperature light and will also open the electrical circuit on the compressor and shutdown the dryer. The dryer will not restart without the customer turning the selector switch to off and then back on. Customer evaluation should be undertaken to determine the cause of the high temperature condition.

After start-up, the high temperature light condition may result from: plugged or dirty condensers, high ambient, high compressed air inlet temperatures or high compressed air flow.

15.Start Timer:

Standard on 2500 SCFM and larger dryers, This timing device is used in conjunction with the High Temperature Control in item 14.

During start-up, this device will temporarily energize the compressor(s) electrical circuit. The start timer is factory set to allow adequate time for the refrigeration system to reach normal suction gas temperatures. If normal suction gas temperatures do not occur within the factory set time, the compressor will shut-down. This shut-down may be caused by conditions as noted in item 14 above.

7

Image 7
Contents 107 W. Main Street Worthington, PA Phone 724.297.3416 Fax Operating InstructionsContents Foundation IntroductionReceiving LocationElectrical Refrigerant Circuit Compressed AIR CircuitExpansion Valves Low Pressure SwitchHigh Pressure Switch Crankcase Heater Where RequiredOil Sightglass Water Pressure Switch Water Cooled onlyHigh Temperature Control Start TimerSTART-UP SHUT-DOWN Design ConditionsWATER-COOLED Models Cooling Water Requirements Installation of Remote Condenser Optional MaintenanceCooling Water Requirements Dryer running Dryer not runningDryer Water downstreamNot running Power light on but dryerHigh pressure drop across Dryer inlet and outlet