Omega Engineering OMR-6510, OMR-6520 manual RS-485 on OMR, OMR RS-485 Network Configurations

Page 6

1.5RS-485 on OMR

The OMR improves the RS-485 capability for minimizing the user‘s cost. On each OMR module, a half-duplex RS-485 transceiver is used to communicate with other modules. A single twisted pair of wires, which provides standard differential transmission, is used to transmit and receive data between modules. The high input impedance of each OMR receiver allows up to 128 OMR modules on the same RS-485 bus without using a signal repeater.

The maximum transfer rate of OMR is 115.2Kbps, which is lower than the maximum speed of the RS-485 standard. The slew-rate limiter on every RS-485 transceiver of OMR is very useful for transmitting error-free data, minimizing EMI, and reducing reflections caused by improperly terminated cables.

The OMR on a network may not use the same power supply. Therefore, the voltage difference between grounds of the modules may exist.

Excessive output current and power dissipation caused by faults or by bus contention are prevented by the current limiter and the thermal shutdown circuitry inside the OMR.

1.6OMR RS-485 Network Configurations

OMR-6000 series is designed under RS-485 multi-drop network architecture. Up to 256 OMR modules can be controlled in a multi-drop network. The limit of 256 is due to command code. The network can be connected by simple topology (Figure 1-1) or branch topology (Figure 1-2) or free topology (Figure 1-3).

The OMR-6520 and OMR-6510 are the two basic communication modules to construct a RS-485 network. The OMR-6520 is a RS-232 to RS-485/RS-422 converter. The OMR-6520 is used to build a RS-485 port for the host computer by converting standard RS-232 signal into RS-485 signal.

The OMR-6510 is the RS-485 signal repeater, which is used to extend or to lengthen the network distance. An OMR bus can connect up to 256 modules, each segment is up to 128 modules. Whenever the numbers of the modules excess 128, the repeater should be used. In addition, the length of a standard RS-485 bus is up to 4000 feet, the repeater should be used whenever the length of a signal bus is more than 4000 feet.

Host

OMRND-6520-6520

RS-232/RSto RS-485-485/RS-422

Converter

RS-485 bus

Terminator

RS-232

OMR Modules

Figure 1-1 Simple Topology

1-4 Introduction

Image 6
Contents 3581 for Contents What is OMR ? Outstanding Features of OMRIntroduction Introduction OMR-6000 series products overview EIA RS-485 StandardOMR RS-485 Network Configurations RS-485 on OMRConstructing a OMR Network Branch TopologyTermination Bus ShieldingHow to Calculate Checksum Value Format of OMR CommandsPage OMR-6520 What is OMR-6520 ?Features of OMR-6520 OverviewSpecifications of OMR-6520 ² InputLook at OMR-6520 & Pin Assignment Pin Definitions Connection Between Host and OMR-6520Functional Block Diagram Setup Installation Application wiring of OMR-6520 ProgrammingSpecifications of OMR-6510 What is OMR-6510 ?Features of OMR-6510 OMR-6510Tx+ Rx+ RX TXIN+ OMR-6510 Functional Block Diagram GND SW1OFF Software is not necessary +DATA DATA+ Data Data Page Install a Brand New OMR Initialize a Brand-New OMRInstall a Brand-New OMR Equipments for Install a New Module Install a New OMR to a Existing NetworkInitialization Wiring Installing ProcedurePage Execute the OMR Administration Utility Software InstallationHow to Execute the OMR Administration Software UtilityChange RS-232 Communication Port Setting OMR Administration Function OverviewDefault RS-232 Communication Port Setting Search all exist OMR modulesUsing Operations Operation-Run Batch Software Utility Save and Print OMR modules’ information Version Information Software Utility Troubleshooting and Maintenance Using the LED Indication