Thermo Products R-410A installation manual Section IX System START-UP, Energize Crankcase Heater

Page 9

835961-UIM-D-0213

SECTION IX: SYSTEM START-UP

ENERGIZE CRANKCASE HEATER

If this unit is equipped with a crankcase heater for the compressor, a warning label with an adhesive back is supplied in the unit installation instruction packet. This label should be attached to the field supplied disconnect switch where it will be easily seen.

In order to energize the crankcase heater, set the indoor cooling ther- mostat to the OFF position. Close the line power disconnect to the unit.

An attempt to start the compressor without at least 8 hours of crank- case heat will damage the compressor.

WITH POWER TO UNIT AND THERMOSTAT IN COOLING POSITION:

1.In the cooling cycle, discharge gas is pumped to the outdoor coil which is the condenser. The indoor coil is the evaporator.

2.If fan switch is in ON position, a circuit is made through blower relay to provide continuous blower operation.

3.With fan switch in AUTO position, a circuit is made from thermostat cooling contact through blower relay to provide blower operation.

4.System will cycle with thermostat demand to provide cooling as needed.

TABLE 1: R-410A Saturation Properties

Temp °F

Pressure

Temp °F

Pressure

Temp °F

Pressure

Temp °F

Pressure

Temp °F

Pressure

PSIG

PSIG

PSIG

PSIG

PSIG

 

 

 

 

 

45

130

60

170

75

217

90

274

105

341

46

132

61

173

76

221

91

278

106

345

47

135

62

176

77

224

92

282

107

350

48

137

63

179

78

228

93

287

108

355

49

140

64

182

79

232

94

291

109

360

50

142

65

185

80

235

95

295

110

365

51

145

66

188

81

239

96

299

111

370

52

147

67

191

82

243

97

304

112

375

53

150

68

194

83

247

98

308

113

380

54

153

69

197

84

250

99

313

114

385

55

156

70

201

85

254

100

317

115

391

56

158

71

204

86

258

101

322

116

396

57

161

72

207

87

262

102

326.

117

401

58

164

73

211

88

266

103

331

118

407

59

167

74

214

89

270

104

336

119

412

CHARGE COMPENSATOR

(Empty in cooling / full in heating)

(Not included in all Units)

OUTDOOR

COIL

FIELD CONNECTED LINE

4-WAY REVERSING VALVE

FILTER DRYER (Solid core)

INDOOR COIL

LIQUID

SENSOR

SUCTION

COMPRESSOR

 

 

 

ACCUMULATOR

 

 

BI-FLOW

 

BI-FLOW

TXV/CHECK

 

TXV/CHECK

VALVE OR ORIFICE (Heating)

VALVE (Cooling) **

FIGURE 10: Heat Pump Flow Diagram

Johnson Controls Unitary Products

9

Image 9
Contents THGD,F/GHGD/THJD,F/YHJD,F/YHJR/THJR Series Section II SafetyList of Sections List of FiguresRequirements For Installing/Servicing R-410A Equipment Section III Unit InstallationADD-ON REPLACEMENT/RETROFIT LimitationsRoof Installation Ground InstallationUnit Placement Precautions During Line InstallationPrecautions During Brazing Service Valve Precautions During Brazing of LinesSection IV Orifice Installation Section V TXV InstallationsInstall Schrader Valve Core and Orifice as follows Section VII System Charge Section VI EvacuationMeasure Indoor Air Flow Charging the UnitField Connections Control Wiring Field Connections Power WiringSection Viii Electrical Connections General Information & GroundingDehumidification Control CFM Selection Board SettingsEnergize Crankcase Heater Section IX System START-UPSection V System Operation Demand Defrost 13 Seer 1.5 ton, 14.5 Seer 1.5-4 Ton Compressor DelayOperation Defrost CurvesSection VI Instructing the Owner Wiring Diagram Single Phase Demand Defrost Section VII Wiring DiagramControl PNK BLK BRN BLK FAN CAP Compressor Relay CCH FAN ORG Relay UIM-D-0213 Johnson Controls Unitary Products Heat Pump and Supplementary Heat Start-Up Sheet Section Viii Start UP SheetAir Side System Total External Static Pressure York International Corp York Drive Norman, OK Owner Education