3 Installing the Converter
3.3Connecting Directly to a PC
To connect the Isolated
Table 3.1
Pin Number |
|
on Connector | Signal Name |
|
|
2 | TxD |
|
|
3 | RxD |
|
|
4 | RTS |
|
|
7 | GND |
|
|
8 | DCD |
|
|
4.Insert the
5.Connect the supplied power cord to the 120 VAC connector on the converter, and plug the other end into any 120 VAC grounded power source.
6.Turn the converter’s power switch on, and verify that the PWR LED is lit. (Refer to Section 5 “Troubleshooting” if the PWR LED is not lit.)
7.Start your software.
To connect the converter to a PC, follow these steps while refering to Figure 3.3 below:
1.Connect the plug end of an
2.Connect the socket end of the serial cable to an
3.If you are using application software that requires direct DCD/RTS control, set the DCD/RTS switch to RTS and the MAN/AUTO switch to MAN. If you are using application software that does not require the direct DCD/RTS control, set the MAN/AUTO switch to AUTO, and use the BAUD thumbwheel to set the data rate to match that of the application software and the ACCESS devices on the network. (In automatic mode, the converter ignores the setting of the DCD/RTS switch.)
|
|
|
| + | Device |
|
|
| 22 AWG Shielded | - | #1 |
|
|
|
| ||
|
|
|
|
| |
|
| + | 4000 Ft. Maximum |
|
|
|
|
|
|
| |
| Port 4 | SHLD |
|
|
|
| - |
|
|
| |
|
| + |
|
| |
|
| Bus |
|
| |
| Port 3 | SHLD | + | Device | |
| - |
|
| ||
|
|
|
| - | #n |
|
| + |
| Up to 32 devices | |
| Port 2 | SHLD |
| ||
| - |
| |||
|
|
|
| ||
|
|
|
|
| |
| 50 Ft. Maximum |
| To Other |
|
|
|
| + |
|
| |
| Port 1 | SHLD |
|
| |
PC |
|
| |||
- |
|
| |||
with |
|
| Devices |
|
|
Supervisory | Isolated |
|
|
| |
Software |
|
|
| ||
| Converter |
|
|
|
|
Figure 3.2 Connecting the Converter Directly to a PC
Siemens Energy & Automation, Inc. | 5 |