4 Testing ACCESS Devices
4 Testing ACCESS Devices
You can use the Isolated
4.1Prepare Cable
To prepare the cable, follow these steps while referring to Figure 4.1.
1.Select a
2.Strip the insulation from both wires at both ends of the cable, exposing approximately 0.5 inch of metal wire on each.
3.Loosen the screws in the
+ | - |
BLK |
|
WHT |
|
Figure 4.1 Two-Terminal Connector for Test Connection
Use this cable to connect devices to the converter according to the procedures in the remainder of this section.
4.2Testing Static Trip III in Type RL Circuit Breaker
If you are testing a Static Trip III trip unit in a Type RL circuit breaker, follow these steps to connect the trip unit to the converter for 15 VDC power, while referring to Figure 4.2:
1.Plug the connector of the
2.Making sure to observe the polarity of the cable, connect the other end to terminals 2 and 3 on the terminal block for cubicle disconnect. (This terminal block is located on the inside left panel of the Type RL circuit breaker compartment.)
3.Connect an
4.Plug one end of the converter’s power cord into the 120 VAC connection on the converter, and plug the other end into any 120 VAC grounded power source.
5.Turn the power switch on.
6.Using testing software supplied by Siemens, verify that the attached trip unit communicates properly.
Isolated
rear panel
15VDC
+ | - |
|
| OUT |
|
|
| +/- 15 VDC | |
|
|
|
|
| BLK | Data | (+) |
|
|
|
|
| |||
|
|
|
| WHT | Data | ||
|
|
|
|
|
|
| |
| RS485 |
|
|
|
|
| |
| + | _ |
|
| Terminal block | for | |
|
|
|
| cubicle | disconnect | ||
|
|
|
|
| |||
|
|
|
|
| on | ||
|
|
|
|
| Type RL | circuit breaker | |
RS485 |
| RS485 | RS485 | RS485 | compartment | ||
+ _ |
| + _ | + _ | + _ front panel |
|
|
|
Figure 4.2 Test Connection for Static Trip III in Type RL Circuit Breaker
8 | Siemens Energy & Automation, Inc. |