CFM Corporation SHR36, SHR52, SHR42A, SHR48 manual Mantel clearance

Page 15

 

 

 

 

SHR Series Woodburning Fireplaces

Mantel Clearance -

 

Mantel Clearance -

 

No Noncombustible Facing Material

with Noncombustibel Facing Material

 

12"

Combustible

 

12"

 

Combustible Mantel

Mantel and Trim

 

(305mm)

Finished Wall

 

(305mm)

Finished Wall

and Trim

Max.

 

Max.

 

 

 

 

1���"

Header

 

1���"

Header

 

 

 

 

12"

 

Ledge Bracket

 

12"

Ledge Bracket

 

 

 

 

(305mm)

 

Noncombustible

(305mm)

Noncombustible

min.

 

Material

 

min.

Material

 

 

 

 

 

Surround

 

 

Surround

 

*

Face

 

6"

Face

 

 

 

Noncombustible Facing

 

 

 

(159mm)

 

 

 

 

Min.

Material

*Minimum width from top of surround to bottom of screen rail

Fireplace Opening

Fireplace Opening

Must be sealed with non- combustible material

Finished Wall

Ledge Bracket

1"

2x 4 Stud

Finished Wall

Must be sealed with noncombustible

materialFP531

Fig. 24 Mantel clearance.

Finished Wall

Stud

Framing Shield

Finished Wall

Must be sealed with noncombustible material

Noncombus- tible Decorative Facing

Must be Sealed with

Noncombustible

Material

Surround

2 x 4 Header

Ledge Bracket

FP1166

Fig. 26 Fireplace surround flush with finished wall.

FP1277

Fig. 25 SHR52 framing shield may be used to attach finish material.

20001384

15

Image 15
Contents SHR Series Table of Contents Safety InformationSHR36 Series Woodburning Fireplace SHR48 Series Woodburning Fireplace Chase Installation Chimney Requirements Offset Installations 30˚ Elbow OffsetsIllustration Key Ten Foot Rule Planning InformationMounting the Fireplace Planning the Chimney RunInsulating Fireplace Enclosure for Cold Climates InstallationChase Installation Chimney SupportsFirebrick Installation FramingChimney Set-up Cutting the Hole Straight-Up Chimney InstallationOffset Installation Ceiling Chimney Hole Possible ObstructionsInstalling Outside Air Kit Positioning, Safety Strips Securing the FireplaceInstalling the Chimney System Installing the Firestop Spacer Ceiling HoleProper Firestop Spacer Installation Penetrating the Roof Continue Installing Pipe to Complete RunCanadian Requirements For Insulation Shield Additional CeilingsCut and Frame Roof Hole Install Remainder of Chimney SectionsInstalling Top Housing or Termination Installing Chimney in a ChaseMantel clearance Facing on fireplace surround flush with finished wall Example for Common Brick Hearth InstallationSide Wall Protection Example of Determining Hearth Extension EquivalentsMinimum Wall Clearances Minimum Hearth Extension DimensionsSealing detail Installing Line for Gas LogsSHR36/42A/48/52 Woodburning Fireplace Accessory Description Model No AccessoriesSLTCF11 For Majestic Fireplaces PRE-ENGINEERED Fireplace Systems Limited Warranty & 30 Year Protection PlanCFM Corporation