Desa (V)VC42NE, (V)VC42PE Installation for Vertical Termination, Flat Ceiling Installation

Page 13

VENTING INSTALLATION INSTRUCTIONS

Installation for Vertical Termination

13

VENTING INSTALLATION INSTRUCTIONS

Continued

INSTALLATION FOR VERTICAL TERMINATION

Note: Vertical restrictor must be installed in all vertical installations.

1.Determine the route your vertical venting will take. If ceiling joists, roof rafters or other framing will obstruct the venting system, consider an offset (see Figure 19) to avoid cutting load bearing members. Note: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insu- lation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations.

2.Set the fireplace in desired location. Drop a plumb line down from the ceiling to the position of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Roof Flashing

Wall Strap

45° Elbow

Ceiling Firestop

Figure 19 - Offset with Wall Strap and 45° Elbows

Flat Ceiling Installation

1.Cut a 10 3/4" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10 3/4"x10 3/4" (273 mm x 273 mm) inside dimensions, as shown in Figure 9 on page 8 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 20).

2.Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. Be sure all pipe and elbow connections are fully twist-locked (see Figure 8, page 8).

3.Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10 3/4"x10 3/4" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 8.

4.Connect a section of pipe and extend up through the hole.

Note: If an offset is needed to avoid obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.

5.Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the flashing as shown in Figure 19. There must be a 1" clearance from the vent pipe to combustible materials.

6.Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements described in Figure 7 on page 6. Note: You must increase vent height for steep roof pitches. Nearby trees, adjoining rooflines, steep pitched roofs and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.

7.Twist-lock the vent cap onto the last section of vent pipe.

Note: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure and meet the minimum allow- able clearances to combustibles. Do not fill any of the required air spaces with insulation.

If area above is a room or

If area above is not a room, install

insulated area, install firestop

firestop below framed hole.

above framed hole.

 

Figure 20 - Installing Firestop

116237-01A

www.desatech.com

Image 13
Contents For Your Safety What to do if YOU Smell GAS For Your SafetySafety Information Table of ContentsLocal Codes Safety Information Product IdentificationPRE-INSTALLATION Preparation Product FeaturesLocation and Space Requirements Framing and Finishing ClearancesTermination CAP AIR Supply Inlet GAS Meter Location of Termination CAPInstallation Precautions Venting Installation InstructionsHorizontal Termination Installation Installation PlanningInstalling Horizontal Vent Cap Noncombustible Exterior Horizontal Termination Configurations Venting Installation InstructionsCorner Installation Venting with Two 90 Elbows Flat Ceiling Installation Installation for Vertical TerminationVertical V Horizontal H Min Max 12 max 18 max 20 max Vertical Termination ConfigurationsHigh Altitude Installation Fireplace Installation Check GAS Type Venting InstallationInstalling Optional Blower Accessory Desa 5/8 Pipe & Vent KitsModel BKT Installation Fireplace InstallationBlower Wiring Diagram Installing GAS Piping to Fireplace LocationInstallation Items Needed Pressure Testing Gas Supply Piping System Connecting Fireplace to GAS SupplyChecking GAS Connections REMOVING/REPLACING Glass Door Pressure Testing Fireplace Gas ConnectionsRemoving Louver Panels Cleaning Glass Door Installing Lava Rock and Glowing EmbersRemoving Glass Door Wall Switch Installation Installing Brick Liner Models BL42DASA and BL42DHASAOptional Remote Control Installation Model WRC Operating Fireplace Wiring DiagramLighting Instructions To Turn OFF GAS To Appliance Operating Optional Blower AccessoryOptional Remote OperationGlass Door Cleaning MaintenancePilot and Burners LogsObserved Problem Possible Cause Remedy TroubleshootingGas leak. See Warning statement at Service Hints Replacement PartsTechnical Service Parts Under WarrantySpecifications Models VC42NE, VC42PE, VVC42NE and VVC42PE Illustrated Parts BreakdownKEY Part Number Description QTY Parts List19 18 116237-01A KEY Part Number Description Accessories Owners Registration Form Postage Required 116237-01A Keep this Warranty Warranty Information

(V)VC42PE, (V)VC42NE specifications

Desa (V)VC42NE and (V)VC42PE are innovative heating solutions that cater to modern residential and commercial spaces. These advanced units embody a combination of efficiency, sustainability, and user-friendly features, making them highly sought after in the market.

The (V)VC42NE model stands out for its high energy efficiency, designed to provide optimal heating performance while minimizing energy consumption. This unit incorporates state-of-the-art condensing technology, which allows it to extract additional heat from exhaust gases, enhancing its overall energy efficiency. With a commendable seasonal efficiency rating, it is suitable for environments where reduced carbon footprints are a priority.

On the other hand, the (V)VC42PE model is engineered to offer unparalleled versatility. It supports a range of fuel options, including natural gas and propane, making it adaptable to various installations. This flexibility is particularly beneficial for users who may want to switch fuel sources in the future. The (V)VC42PE also includes a powerful fan system, which ensures even heat distribution throughout the space, eliminating cold spots.

Both models are equipped with advanced safety features that comply with stringent industry standards. These include flame failure devices, pressure relief valves, and overheat protection systems that ensure the units operate safely under all conditions. Additionally, they are designed for low maintenance, with accessible components that simplify servicing and repairs.

One of the standout characteristics of both Desa models is their intuitive control systems. The units feature digital thermostats that allow users to set and monitor temperatures effortlessly. Moreover, they offer programmable settings that enable users to optimize heating schedules according to their lifestyle needs. This feature contributes to enhanced comfort while further promoting energy savings.

In terms of design, both the (V)VC42NE and (V)VC42PE models possess a sleek, modern aesthetic that integrates seamlessly into various interior styles. Their compact size allows for easy installation in tight spaces, making them an ideal choice for apartments, offices, and other limited areas.

In summary, Desa (V)VC42NE and (V)VC42PE units are exemplary heating systems that combine efficiency, safety, and user-friendly features, making them suitable for a wide range of applications. With their advanced technologies and commitment to sustainability, these models are poised to meet the demands of today's energy-conscious consumers.