AIR FOR COMBUSTION AND VENTILATION

Ventilation Air

INSTALLATION

Check Gas Type

7

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 5). You can also remove door into adjoining room (see option 3, Figure 5). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/ NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 6 - Ventilation Air from Outdoors Shown with Optional Mantel

INSTALLATION

NOTICE: This heater is intended for use as supple- mental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.

WARNING: A qualified service person must in- stall fireplace. Follow all local codes.

12"

Figure 5 - Ventilation Air from Inside Building Shown with Optional Mantel

Note: Your Comfort Glow fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against any exterior surface of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.

Use the dimensions shown for rough openings to create the easiest installation (see Built-In Fireplace Installation, page 9)

CHECK GAS TYPE

Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.

For morevisit www..com

111044-01A

Image 7
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualSafety Information Table of ContentsProduct Identification Local CodesAssembly Product FeaturesUnpacking Unusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Assembling HoodConfined and Unconfined Space Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building InstallationVentilation AIR Check GAS TypeLocating Fireplace Installation ItemsRough Opening for Installing in Wall BUILT-IN Fireplace InstallationOptional Mantel Installation Mantel Clearances for BUILT-IN InstallationRemoving Upper Louver Assembly Installing Blower Accessory GA3450TRemoving Valve Cover Shield Installing Blower AssemblyOutlet For Built-In InstallationAttaching Wood Base to Solid Floor Connecting to GAS SupplyExtension Cord Installation Items Needed Connecting Equipment Shutoff Valve to Heater ControlPressure Testing Fireplace Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Operating Fireplace For Your Safety Read Before LightingLighting Instructions Inspecting Burner Air Passageways Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole CabinetObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at Technical Service SpecificationsReplacement Parts Service HintsModels CGCF26TP and CGCF26TN Illustrated Parts BreakdownKEY CGCF26TP CGCF26TN Description QTY Parts ListParts Centrals Owners Registration Form Postage Required Accessories Warranty Information