OWNER’S MANUAL
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces
Ventilation |
|
Grills | Or |
into Adjoining | Remove |
Room, | Door into |
Option 1 | Adjoining |
| Room, |
| Option 3 |
12"
Ventilation Grills
Into Adjoining Room,
Option 2
(see options 1 and 2, Figure 5). You can also remove door into adjoining room (see op- tion 3, Figure 5). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
12"
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a
Figure 5 - Ventilation Air from Inside Building Shown with Optional Mantel
Ventilated
Outlet Attic
Air
Outlet |
|
Air | To Attic |
|
To
Crawl
Space
Inlet
Air
Inlet Air |
| Ventilated |
|
| Crawl Space |
|
|
Figure 6 - Ventilation Air from Outdoors Shown with Optional Mantel
107035 | 7 |