Desa VC42NE SERIES Installation for vertical termination, Flat Ceiling Installation

Page 15

Venting Installation

instructions

Continued

installation for vertical termination

Note: Vertical restrictor must be installed in all vertical installations.

1.Determine the route your vertical venting will take. If ceiling joists, roof rafters or other framing will obstruct the venting system, consider an offset (see Figure 19) to avoid cut- ting load bearing members. Note: Pay special attention to these installation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum vertical rise of the venting system and any maximum horizontal offset limitations.

2.Set the fireplace in desired location. Drop a plumb line down from the ceiling to the posi- tion of the fireplace exit flue. Mark the center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.

Drop a plumb line from the inside of the roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.

Roof Flashing

Wall Strap

45° Elbow

Ceiling Firestop

Figure 19 - Offset with Wall Strap and 45°

Elbows

Flat Ceiling Installation

1. Cut a 10 3/4" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 10 3/4" x 10 3/4" (273 mm x 273 mm) inside dimensions, as shown in Figure 9 on page 10 using framing lumber the same size as the ceiling joists. If the area above the ceiling is an insulated ceiling or a room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise, install firestop below the framed hole. The firestop should be installed with no less than three nails per side (see Figure 20).

2. Assemble the desired lengths of pipe and elbows necessary to reach from the fireplace flue up through the firestop. Be sure all pipe and elbow connections are fully twist-locked (see Figure 8, page 10).

3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed open vent pipes before cutting hole in roof.) The 10 3/4" x 10 3/4" hole must be measured on the horizontal; actual length may be larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 10.

4. Connect a section of pipe and extend up through the hole.

Note: If an offset is needed to avoid obstruc- tions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Fig- ure 19). Whenever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less restriction to the flow of the flue gases and intake air.

If area above is a room or insulated area, install firestop above framed hole.

If area above is not a room, install firestop below framed hole.

Figure 20 - Installing Firestop

116237-01E

www.desatech.com

15

Image 15
Contents What to do if YOU Smell GAS Table of Contents Safety Information Product IdentificationHigh traffic areas Location and space requirements Product FeaturesPre-Installation Preparation Local CodesVenting clearances Clearances42 1067 mm Front 36 914 mm Top of Standoffs Vent See ventingFraming and finishing Noncombustible mantels at any height aboveFireplace Termination CAP AIR Supply Inlet GAS Meter Location of Termination CapInstallation Precautions Venting Installation InstructionsInstallation Planning Installing Horizontal Vent Cap Noncombustible Exterior Ground Floor Installation Recommended Applications Corner ground floor installation Corner InstallationHorizontal System Installation Using TWO 90 Elbows Installation for vertical termination Flat Ceiling InstallationConnect a section of pipe and extend up through the hole Twist-lock the vent cap onto the last section of vent pipe Vertical Venting High Altitude InstallationDesa 5/8 Pipe & Vent Kits Number Description Parts list for venting kits and componentsPlug in blower power cord Fireplace InstallationInstalling optional blower accessories Model BK InstallationBlower Model BKT Model BKT InstallationInstalling Gas Piping to Fireplace Location Blower Wiring DiagramInstallation Items Needed Propane/LP Supply TankExternal Regulator Vent Pointing Down Connecting Fireplace to GAS SupplyDisconnect fireplace and its individual equip Checking GAS ConnectionsTest Pressures Equal To or Less Than Psig 3.5 kPa Close equipment shutoff valve see FigureRemoving Glass Door Pressure Testing Fireplace Gas ConnectionsRemoving/Replacing Glass Door Removing Louver PanelsInstalling lava rock and glowing embers Installing Brick liner Models BL42DASA and BL42DHASACleaning Glass Door Wall Switch Installation Optional Remote control Installation model WRCReplace top and bottom louvers Wiring Diagram To Turn OFF GAS To Appliance For your safety Read before lightingOperating Fireplace Lighting InstructionsOptional Remote Operation Operating optional blower accessoryPilot Assembly Inspecting BurnersLogs Cleaning MaintenanceGlass Door Pilot and burnersTroubleshooting Observed Problem Possible Cause RemedyVenting system Pilot will not stay lit Check wiring connectionUle And/or check ground wire to No gas to burner, although wall Wall switch wires defectiveGas leak. See Warning Statement at topSpecifications Replacement PartsService Hints Technical ServiceAccessories Models VC42NE, VVC42NE, VC42PE and VVC42PE Illustrated Parts BreakdownParts List 2827 19 18 Burner Pan Assembly Warranty Information Keep this WarrantyLimited Warranty DIRECT-VENT Fireplace