11.3Outdoor Unit

11.3.1Install the Outdoor Unit

šAfter selecting the best location, start installation according to indoor/outdoor unit installation diagram. 1 Fix the unit on concrete or rigid frame firmly and horizontally by bolt nut (ø13/32").

2 When installing at roof, please consider strong wind and earthquake. Please fasten the installation stand firmly with bolt or nails.

Model

A

B

C

D

E9NKUA, E12NKUA

22-7/16"

4-1/8"

23/32"

12-19/32"

11.3.2Connect the Piping

11.3.2.1Connecting the piping to indoor

Please make flare after inserting flare nut (locate at joint portion, of tube assembly) onto the copper pipe. (In case of using long piping)

Connect the piping

šAlign the center of piping and sufficiently tighten the flare nut with fingers.

šFurther tighten the flare nut with torque wrench in specified torque as stated in the table.

Do not over tighten, over tightening may cause gas leakage.

Piping size

Torque

1/4"

13.3 Ibf.ft

3/8”

31.0 Ibf.ft

1/2"

40.6 Ibf.ft

5/8”

47.9 Ibf.ft

3/4"

73.8 Ibf.ft

11.3.2.2Connecting the piping to outdoor

Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge.

Make flare after inserting the flare nut (locate at valve) onto the copper pipe.

Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table.

26

Image 26
Contents CS-E9NKUAW CU-E9NKUA CS-E12NKUAW CU-E12NKUA Exploded View and Replacement Parts List Safety Precautions Page Specification CU-E9NKUA CU-E12NKUA ARIType Propeller Fan Material Motor Type DC 8 poles DRY Bulb WET Bulb Features š Easy to use remote control š Quality ImprovementIndoor Unit Outdoor Unit Remote Control Location of Controls and ComponentsDimensions Indoor UnitOutdoor Unit Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Outdoor Unit Electronic Circuit Diagram Outdoor Unit Printed Circuit Board Main Printed Circuit BoardPower Printed Circuit Board Indicator Printed Circuit Board Outdoor Unit Select the Best Location Installation InstructionIndoor/Outdoor Unit Installation Diagram Indoor UnitHow to Fix Installation Plate To Drill a Hole in the Wall and Install a Sleeve of PipingIndoor Unit Installation Connect the Cable to the Indoor Unit Wiring Stripping and connecting requirement Cutting and flaring the pipingInstall the Outdoor Unit Connect the PipingConnecting the piping to outdoor multi Evacuation of the equipmentConnect the Cable to the Outdoor Unit Operation Control Basic FunctionIndoor Fan Motor Operation Basic Rotation Speed rpmVertical Airflow Outdoor Fan Motor OperationAirflow Direction Horizontal Airflow Quiet Operation Cooling Mode/Cooling Area of Dry ModeQuiet Operation Heating On Timer Control Powerful Mode OperationTimer Control OFF Timer ControlIndication Panel Soft Dry Operation Operation Control For Multi Split ConnectionCooling operation Heating OperationAutomatic Operation Residual Heat Removal ControlProtection Control Protection Control For All OperationsCompressor Overheating Prevention Control Outdoor Air Temperature ControlProtection Control For Cooling & Soft Dry Operation Low Pressure Prevention Control Gas Leakage DetectionDew Prevention Control Cooling Overload ControlFreeze Prevention Control Protection Control For Heating OperationOutdoor Air Temperature Control Servicing Mode Auto Off/On ButtonRemote Control Button Troubleshooting Guide Refrigeration Cycle SystemPage Self Diagnosis Function Three Digits Alphanumeric Code To Display Memorized Error Code Protective OperationBreakdown Self Diagnosis Function To Make a DiagnosisError Code Table Page Self-diagnosis Method 16.4.1 H11 Indoor/Outdoor Abnormal Communication16.4.2 H12 Indoor/Outdoor Capacity Rank Mismatched 16.4.3 H14 Indoor Intake Air Temperature Sensor Abnormality 16.4.4 H15 Compressor Temperature Sensor Abnormality 16.4.5 H16 Outdoor Current Transformer Open Circuit 16.4.6 H19 Indoor Fan Motor DC Motor Mechanism Locked 16.4.7 H23 Indoor Pipe Temperature Sensor Abnormality 16.4.8 H27 Outdoor Air Temperature Sensor Abnormality 16.4.9 H28 Outdoor Pipe Temperature Sensor Abnormality Malfunction Decision Conditions Malfunction Decision Conditions 16.4.12 H33 Unspecified Voltage between Indoor and Outdoor 16.4.13 H36 Outdoor Gas Pipe Sensor Abnormality Malfunction Decision Conditions 16.4.15 H97 Outdoor Fan Motor DC Motor Mechanism Locked 16.4.16 H98 Indoor High Pressure Protection Malfunction Decision Conditions 16.4.18 F11 Indoor Pipe Temperature Sensor Abnormality 16.4.19 F17 Indoor Standby Units Freezing Abnormality Remark16.4.20 F90 Power Factor Correction Protection 16.4.21 F91 Refrigeration Cycle Abnormality 16.4.22 F93 Compressor Rotation Failure 16.4.23 F95 Cooling High Pressure Abnormality 16.4.24 F96 IPM Overheating 16.4.25 F97 Compressor Overheating 16.4.26 F98 Input Over Current Detection 16.4.27 F99 Output Over Current Detection Disassembly and Assembly Instructions To remove front grilleTo remove discharge grille Page Page CS-E9NK CU-E9NK Technical DataOperation Characteristics 139.500 139.000 Piping Length ft 600 Current 400 300 200 100 Page Page CS-E12NK CU-E12NK Page Page Page Exploded View and Replacement Parts List Chassis Complete Outdoor Unit Chassis Assy
Related manuals
Manual 12 pages 57.08 Kb

CS-E9NKUAW, CU-E9NKUA, CU-E12NKUA, CS-E12NKUAW specifications

Panasonic has established itself as a leader in the air conditioning market, offering a range of products that combine advanced technology with energy efficiency. The Panasonic models CS-E12NKUAW, CU-E12NKUA, CU-E9NKUA, CSU-2E18NBU, and CS-E9NKUAW exemplify this commitment to quality and innovation.

The CS-E12NKUAW and CS-E9NKUAW are split-type air conditioners designed for residential use. One of the standout features of these models is their energy-efficient inverter technology. This innovation allows the compressor to adjust its speed according to the cooling demand, leading to lower energy consumption and cost savings for homeowners. Additionally, these units operate quietly, ensuring a peaceful environment while effectively maintaining comfortable temperatures.

The CU-E12NKUA and CU-E9NKUA are the corresponding outdoor units that support the indoor models. These units are designed for durability and performance, using robust materials that withstand various weather conditions. Panasonic's outdoor units are equipped with a reliable cooling system that enhances the overall efficiency and longevity of the air conditioning system.

The CSU-2E18NBU model is perfect for larger spaces, handling greater loads while ensuring consistent cooling. This unit also leverages inverter technology for efficient operation. The CSU models often include advanced features such as a high-density filter that captures dust and allergens, promoting a healthier indoor environment.

All these units are designed with user-friendly interfaces, allowing for easy temperature control and adjustments. Many of the models also come with remote control options, enabling users to regulate their comfort from the convenience of their seat. Additionally, advanced air purifying technology enhances indoor air quality by eliminating harmful pollutants and odors.

Panasonic air conditioners are known for their environmentally friendly refrigerants, contributing to a reduced carbon footprint and compliance with international standards. These features reflect Panasonic's commitment to sustainability and innovation, making these models a leading choice for consumers looking to balance comfort, efficiency, and environmental responsibility.

In summary, Panasonic's CS-E12NKUAW, CU-E12NKUA, CU-E9NKUA, CSU-2E18NBU, and CS-E9NKUAW models represent some of the best in today's air conditioning market, with key features including energy efficiency, user-friendly controls, advanced air purification, and robust outdoor units designed for performance and reliability. These units provide an ideal solution for maintaining a comfortable home environment while being conscious of energy use and environmental impact.