Panasonic CS-E12NKUAW, CU-E12NKUA, CU-E9NKUA, CS-E9NKUAW service manual Safety Precautions

Page 3

1. Safety Precautions

šRead the following “SAFETY PRECAUTIONS” carefully before perform any servicing.

šElectrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed.

šThe caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.

WARNING

CAUTION

This indication shows the possibility of causing death or serious injury

This indication shows the possibility of causing injury or damage to properties.

šThe items to be followed are classified by the symbols:

This symbol denotes item that is PROHIBITED from doing.

šCarry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.

WARNING

1.Do not modify the machine, part, material during repairing service.

2.If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.

3.Do not wrench the fasten terminal. Pull it out or insert it straightly.

4.Engage authorized dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause water leakage, electrical shock or fire.

5.Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.

6.Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock.

7.Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.

8.For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.

9.This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.

10.Do not use joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to installation instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.

11.Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up or fire at the connection point of terminal, fire or electrical shock.

12.When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration cycle (piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).

13.Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb up to outdoor unit and cross over the handrail and causing accident.

14.This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may cause electrical shock in case equipment breakdown or insulation breakdown.

15.Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.

16.Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.

17.Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may break and cause refrigerant gas leakage.

18.For R410A models, when connecting the piping, do not use any existing (R22) pipes and flares nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. In case of using existing (R22) pipes during installation of R410A models, must carry out pump down properly to collect back the refrigerant and oil before installation new unit.

Thickness of copper pipes used with R410A must be more than 1/64". Never use copper pipes thinner than 1/64". It is desirable that the amount of residual oil is less than 0.0014 oz/32.8ft.

3

Image 3
Contents CS-E9NKUAW CU-E9NKUA CS-E12NKUAW CU-E12NKUA Exploded View and Replacement Parts List Safety Precautions Page CU-E9NKUA CU-E12NKUA ARI SpecificationType Propeller Fan Material Motor Type DC 8 poles DRY Bulb WET Bulb š Easy to use remote control š Quality Improvement FeaturesLocation of Controls and Components Indoor Unit Outdoor Unit Remote ControlIndoor Unit DimensionsOutdoor Unit Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Outdoor Unit Electronic Circuit Diagram Outdoor Unit Main Printed Circuit Board Printed Circuit BoardPower Printed Circuit Board Indicator Printed Circuit Board Outdoor Unit Indoor Unit Installation InstructionIndoor/Outdoor Unit Installation Diagram Select the Best LocationTo Drill a Hole in the Wall and Install a Sleeve of Piping How to Fix Installation PlateIndoor Unit Installation Connect the Cable to the Indoor Unit Cutting and flaring the piping Wiring Stripping and connecting requirementConnect the Piping Install the Outdoor UnitEvacuation of the equipment Connecting the piping to outdoor multiConnect the Cable to the Outdoor Unit Basic Function Operation ControlBasic Rotation Speed rpm Indoor Fan Motor OperationOutdoor Fan Motor Operation Airflow DirectionVertical Airflow Quiet Operation Cooling Mode/Cooling Area of Dry Mode Quiet Operation HeatingHorizontal Airflow OFF Timer Control Powerful Mode OperationTimer Control On Timer ControlIndication Panel Heating Operation Operation Control For Multi Split ConnectionCooling operation Soft Dry OperationResidual Heat Removal Control Automatic OperationProtection Control For All Operations Protection ControlLow Pressure Prevention Control Gas Leakage Detection Outdoor Air Temperature ControlProtection Control For Cooling & Soft Dry Operation Compressor Overheating Prevention ControlProtection Control For Heating Operation Cooling Overload ControlFreeze Prevention Control Dew Prevention ControlOutdoor Air Temperature Control Auto Off/On Button Servicing ModeRemote Control Button Refrigeration Cycle System Troubleshooting GuidePage To Make a Diagnosis To Display Memorized Error Code Protective OperationBreakdown Self Diagnosis Function Self Diagnosis Function Three Digits Alphanumeric CodeError Code Table Page 16.4.1 H11 Indoor/Outdoor Abnormal Communication Self-diagnosis Method16.4.2 H12 Indoor/Outdoor Capacity Rank Mismatched 16.4.3 H14 Indoor Intake Air Temperature Sensor Abnormality 16.4.4 H15 Compressor Temperature Sensor Abnormality 16.4.5 H16 Outdoor Current Transformer Open Circuit 16.4.6 H19 Indoor Fan Motor DC Motor Mechanism Locked 16.4.7 H23 Indoor Pipe Temperature Sensor Abnormality 16.4.8 H27 Outdoor Air Temperature Sensor Abnormality 16.4.9 H28 Outdoor Pipe Temperature Sensor Abnormality Malfunction Decision Conditions Malfunction Decision Conditions 16.4.12 H33 Unspecified Voltage between Indoor and Outdoor 16.4.13 H36 Outdoor Gas Pipe Sensor Abnormality Malfunction Decision Conditions 16.4.15 H97 Outdoor Fan Motor DC Motor Mechanism Locked 16.4.16 H98 Indoor High Pressure Protection Malfunction Decision Conditions 16.4.18 F11 Indoor Pipe Temperature Sensor Abnormality Remark 16.4.19 F17 Indoor Standby Units Freezing Abnormality16.4.20 F90 Power Factor Correction Protection 16.4.21 F91 Refrigeration Cycle Abnormality 16.4.22 F93 Compressor Rotation Failure 16.4.23 F95 Cooling High Pressure Abnormality 16.4.24 F96 IPM Overheating 16.4.25 F97 Compressor Overheating 16.4.26 F98 Input Over Current Detection 16.4.27 F99 Output Over Current Detection To remove front grille Disassembly and Assembly InstructionsTo remove discharge grille Page Page Technical Data Operation CharacteristicsCS-E9NK CU-E9NK 139.500 139.000 Piping Length ft 600 Current 400 300 200 100 Page Page CS-E12NK CU-E12NK Page Page Page Exploded View and Replacement Parts List Chassis Complete Outdoor Unit Chassis Assy
Related manuals
Manual 12 pages 57.08 Kb

CS-E9NKUAW, CU-E9NKUA, CU-E12NKUA, CS-E12NKUAW specifications

Panasonic has established itself as a leader in the air conditioning market, offering a range of products that combine advanced technology with energy efficiency. The Panasonic models CS-E12NKUAW, CU-E12NKUA, CU-E9NKUA, CSU-2E18NBU, and CS-E9NKUAW exemplify this commitment to quality and innovation.

The CS-E12NKUAW and CS-E9NKUAW are split-type air conditioners designed for residential use. One of the standout features of these models is their energy-efficient inverter technology. This innovation allows the compressor to adjust its speed according to the cooling demand, leading to lower energy consumption and cost savings for homeowners. Additionally, these units operate quietly, ensuring a peaceful environment while effectively maintaining comfortable temperatures.

The CU-E12NKUA and CU-E9NKUA are the corresponding outdoor units that support the indoor models. These units are designed for durability and performance, using robust materials that withstand various weather conditions. Panasonic's outdoor units are equipped with a reliable cooling system that enhances the overall efficiency and longevity of the air conditioning system.

The CSU-2E18NBU model is perfect for larger spaces, handling greater loads while ensuring consistent cooling. This unit also leverages inverter technology for efficient operation. The CSU models often include advanced features such as a high-density filter that captures dust and allergens, promoting a healthier indoor environment.

All these units are designed with user-friendly interfaces, allowing for easy temperature control and adjustments. Many of the models also come with remote control options, enabling users to regulate their comfort from the convenience of their seat. Additionally, advanced air purifying technology enhances indoor air quality by eliminating harmful pollutants and odors.

Panasonic air conditioners are known for their environmentally friendly refrigerants, contributing to a reduced carbon footprint and compliance with international standards. These features reflect Panasonic's commitment to sustainability and innovation, making these models a leading choice for consumers looking to balance comfort, efficiency, and environmental responsibility.

In summary, Panasonic's CS-E12NKUAW, CU-E12NKUA, CU-E9NKUA, CSU-2E18NBU, and CS-E9NKUAW models represent some of the best in today's air conditioning market, with key features including energy efficiency, user-friendly controls, advanced air purification, and robust outdoor units designed for performance and reliability. These units provide an ideal solution for maintaining a comfortable home environment while being conscious of energy use and environmental impact.