8-5. Trouble Diagnosis of Fan Motor

This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor.

Perform the trouble diagnosis by Test Run mode described on Installation Instructions of indoor unit.

Important: (A) Turn OFF the power before connecting or disconnecting the motor connectors.

(B)When performing voltage measurement at the outdoor controller connector for (3) in the table below, the DC motor will trip and voltage output will stop approximately 10 seconds after operation is started. For this reason, to measure the voltage again, first turn OFF the outdoor unit power, then, measure the voltage in Test Run mode.

[Trouble symptom 1] The fan does not stop when the outdoor unit stops. Outdoor unit controller trouble

[Trouble symptom 2] The fan motor does not rotate when the outdoor unit is operating.

(Diagnostic procedure)

*Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor unit controller (3 locations).

Measurement location

Normal value

(1) Vm-Gnd: Between pin 1 and pin 4

DC 230V or more

(2) Vcc-Gnd: Between pin 5 and pin 4

DC 14V or more

(3) Vsp-Gnd: Between pin 7 and pin 4

After fluctuating 4 times between DC 1.7 to 6.1V

 

(1 sec. ON) and DC 0 V (1 sec. OFF), the DC

 

motor trips.

 

 

(Diagnostic results)

All of the above measured values are normal. Fan motor trouble (Replace the motor.) Any one of the above measured values is not normal. Outdoor unit controller trouble

(Replace the controller .)

(Reference) DC motor connector pin arrangement

Pin 1: Vm (red)

Pin 2: Not used

Pin 3: Not used

Pin 4: Gnd (blue)

Pin 5: Vcc (brown)

Pin 6: PG (white)

Pin 7: Vsp (orange)

[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the outdoor unit operates.

(There is trouble in the system that provides feedback of motor rotation speed from the motor to the outdoor unit controller.)

[Trouble symptom 4] Fan motor rotation speed does not change during outdoor unit operation.

[Trouble symptom 5] Fan motor rotation speed varies excessively during outdoor unit operation.

(Remedy for symptom 3 to 5)

It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble. Therefore, first replace the outdoor unit controller, then (if necessary) replace the DC motor.

87

Image 87
Contents DC Inverter MULTI-SYSTEM AIR Conditioner Safety Precautions Prohibit Table of Contents Appendix a Semi-Concealed Type Wall Mounted TypeOperating Range Duct Less Type Rated 230V Unit SpecificationsOutdoor Unit CU-3KE19NBU Indoor Unit CS-MKE9NKU ×Indoor Unit Outdoor Unit208V CU-4KE24NBU Running Amperes 10.1 Running Amperes 10.0 11.1 CU-4KE31NBU Running Amperes 12.3 10.3 Running Amperes 12.7 11.4 Outdoor Unit Major Component SpecificationsOutdoor Unit CU-4KE24NBU Outdoor Unit CU-4KE31NBU CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU Other Component SpecificationsDimensional Data Unit inchmm 852-0-0010-20400-0 Unit inchmm 852-0-0010-20300-0 Refrigerant Flow Diagram Insulation of Refrigerant TubingIndoor unit Outdoor unit Valve Narrow tube Curve because it can cause the tube to break or crack Temperature Charts Temperature Charts CU-3KE19NBUIndoor Unit CS-MKE7NKU × F21 Outdoor Unit CU-3KE19NBU Indoor Unit CS-MKE12NKU × Heating CharacteristicsIndoor Unit CS-MKE18NKU × Indoor Unit CS-MKE9NB4U × Outdoor Unit CU-3KE19NBU Indoor Unit CS-MKE12NB4U × Indoor Unit CS-KE12NB4UW × Temperature Charts CU-4KE24NBU 188 Lo fan Hi fan HH fan Outdoor Unit CU-4KE24NBU Indoor Unit CS-MKE12NKU × Indoor Unit CS-MKE18NKU × Indoor Unit CS-MKE24NKU × 23C 73F Current 21C Temp 70F 17C Air Indoor 63F Outdoor Unit CU-4KE24NBU Indoor Unit CS-MKE12NB4U × Indoor Unit CS-KE12NB4UW × Temperature Charts CU-4KE31NBU Wide 362 Pressure 290 High 218 Outdoor air temperature F C 73F 23C Temp Indoor 73F 23C Air Temp 86F 30C Temp Air Indoor 63F Wide 362 Current Indoor Outdoor Cooling CapacityCS-MKE12NB4U × Power Supply 230V Single Phase 60Hz Cooling CapacityCS-MKE9NKU × CS-KE18NB4UW + CS-MKE12NB4U + CS-MKE12NB4U 30,600 BTU/h CS-MKE9NB4U × Cooling Capacity Low Ambient TC Total Cooling Capacity BTU/h ENT. TEMP. o F o C Ambient TEMP. o F o C 12.8 23,390 23,310 18,570 22,160 24,260 30,760 22,560 28,790 22,730 TH Total Heating Capacity BTU/h Heating CapacityPower Supply 230V Single Phase 60Hz Heating Capacity 29,200 BTU/h 28,400 BTU/h 32,000 BTU/h 000 CFM Outdoor Unit CU-3KE19NBU 8FA2-5251-11700-1 Electric Wiring DiagramsOutdoor Unit CU-4KE24NBU 8FA2-5251-11500-1 Outdoor Unit CU-4KE31NBU 8FA2-5251-11300-1 Explanation of Functions FunctionsStop Cool Frequency control Fluctuation fanFluctuation fan Low Ambient Cooling Operation Non-stop defrosting Clean defrostProtective Functions Defrost Detection and ReleaseCurrent control Current ControlDescription of function Automatic frequency controlControl at Heat Start-up Compressor Temperature ControlReset conditions Low Start CurrentPrecautions before Performing Inspection or Repair Troubleshooting Before Calling for ServiceTrouble Diagnosis by Error Monitor Lamps Location of the Error Monitor LampsDisplay of the Error Monitor Lamps Checking the defrost operation Work procedure Check items unit operationChecking the Outdoor System Checking the outdoor unitTrouble Diagnosis of Each Part Problems of Each Part and Inspection PointsInspection Points for Each Part CU-3KE19NBU MV0 MV1 MV2 CU-4KE24NBU CU-4KE31NBU Electric expansion valveBranch tubing temperature sensor BreakerRefrigerant gas pressure Trouble Diagnosis of Fan Motor Diagnostic procedureDiagnostic results Remedy for symptom 3 toComponents mixing proportions Characteristics of New Refrigerant R410AWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorR410A from changing Amount in the charging cylinder is less than 20%Example To prevent the compositionCase Refrigerant is Leaking Welding leaking pointsRecharging Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing SystemsPage 852-6-4190-584-00-2 For Outdoor Unit ContentsPlease Read Before Starting ‡ 8VHWKHIODUHPHWKRGIRUFRQQHFWLQJWXELQJ Fins of the outdoor unit. You may get injuredGeneral For ceiling-mounted cassette units Installation Site SelectionIndoor Unit For wall-mounted unitsH1, H2, H3, H4 Connecting Indoor Units Connecting indoor unit for CU-3KE19NBUConnecting indoor unit for CU-4KE24NBU 815.88mm Locally purchased Connecting indoor unit for CU-4KE31NBU CS-MKE24NKU Back Baffle Plate for the Outdoor UnitIt is recommended to use baffle plates FrontAir Discharge Baffle Air Intake BafflePrecautions for installation CU-4KE31NBU Outer Dimensions of Outdoor UnitCU-3KE19NBU CU-4KE24NBUNever install only a single indoor unit Diagram of Outdoor Unit InstallationInstallation Process Flaring Procedure with a Flare ToolUse of the Flaring Method Tubing Connections To 0.5 mm Adjust so that the amount of tube For ceiling-mounted cassette units Insulation of Refrigerant TubingTo prevent heat loss and wet floors due to dripping of con  For wall-mounted unitsFinishing the Installation Air Purging Air Purging with a Vacuum Pump for Test Run Adapter manual, and use the adapter correctly External diameter of service port R410A 5/16If pump-down is not possible What is pump-down?Pump-down procedure  Pump DownWiring Instructions General Precautions on WiringRecommended Wire Length and Diameter Disconnect switch may be required by national or local codes For Indoor Unit How to connect wiring to the terminalFor Outdoor Unit  For solid core wiring or F-cable  For stranded wiringIndoor unit C Wiring Instructions for the Outdoor UnitIndoor unit D Indoor unit BChecking tubing and wiring Test RunPerforming a test run Installation Check Sheet Connecting a Home Automation DeviceDC1111-0
Related manuals
Manual 114 pages 38.6 Kb Manual 56 pages 332 b

CU-3KE19NBU, CU-4KE24NBU, CU-4KE31NBU specifications

The Panasonic CU-4KE24NBU, CU-4KE31NBU, and CU-3KE19NBU are high-efficiency air conditioning units that represent Panasonic's commitment to innovative climate control solutions. These models integrate advanced technologies to deliver superior performance, energy savings, and user comfort, making them ideal for both residential and commercial applications.

The CU-4KE24NBU, a part of the ECOi series, is designed for medium-sized spaces. It boasts an impressive cooling capacity, ensuring optimal temperature regulation. Its inverter technology adjusts the compressor speed according to the needs of the environment, resulting in reduced energy consumption and consistent comfort levels. The unit operates quietly, making it suitable for bedrooms, offices, or other noise-sensitive environments. Additionally, it features a robust air filtration system that improves indoor air quality by removing dust and allergens.

The CU-4KE31NBU offers a slightly higher capacity, making it perfect for larger areas. Like its counterpart, it utilizes inverter technology, which not only enhances energy efficiency but also minimizes wear and tear on the components, leading to a longer lifespan. Its multi-split capability allows for the connection of multiple indoor units to a single outdoor unit, providing flexibility in installation. The CU-4KE31NBU also integrates smart technology that allows users to control the system remotely via smartphones, giving them greater convenience and control over their environment.

For applications requiring a more compact option, the CU-3KE19NBU is an excellent choice. This model balances size and power, offering a competitive cooling capacity that can easily service small to medium-sized rooms. The unit is designed for easy installation and maintenance, featuring a lightweight construction that simplifies handling by technicians. The efficient inverter technology ensures that users benefit from lower energy bills while maintaining a consistent indoor climate.

All three models are equipped with Panasonic’s advanced refrigerants, which contribute to their eco-friendly performance. These refrigerants help reduce greenhouse gas emissions while maintaining high efficiency. Moreover, the units come with built-in diagnostic capabilities, allowing for quick detection of any issues, thus ensuring that the systems operate at peak efficiency throughout their lifespan.

In summary, the Panasonic CU-4KE24NBU, CU-4KE31NBU, and CU-3KE19NBU are exemplary air conditioning solutions that combine cutting-edge technology with user-friendly features, ensuring that they meet the varying needs of today's consumers while promoting energy efficiency and sustainability.