Panasonic CS-XE12PKUA manual Protection Control For All Operations, Total Running Current

Page 44

13. Protection Control

13.1 Protection Control For All Operations

13.1.1Restart Control (Time Delay Safety Control)

šThe Compressor will not turn on within 3 minutes from the moment operation stops, although the unit is turned on again by pressing OFF/ON button at remote control within this period.

šThis control is not applicable if the power supply is cut off and on again.

šThis phenomenon is to balance the pressure inside the refrigerant cycle.

13.1.2Total Running Current

1When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will be decreased.

2If the running current does not exceed X value for 5 seconds, the frequency instructed will be increased.

3However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.

Model

XE9PKUA

XE12PKUA

Operation Mode

X (A)

Y (A)

X (A)

Y (A)

Cooling / Soft Dry (A)

6.48

15.00

7.70

15.00

Cooling / Soft Dry (B)

6.48

15.00

7.70

15.00

Heating

7.48

15.00

9.20

15.00

Cooling / Soft Dry (C)

6.48

15.00

7.70

15.00

4 The first 30 minutes of cooling operation, (A) will be applied.

13.1.3IPM (Power transistor) Prevention Control

šOverheating Prevention Control

1When the IPM temperature rises to 248°F (120°C), compressor operation will stop immediately.

2Compressor operation restarts after 3 minutes the temperature decreases to 230°F (110°C).

3If this condition repeats continuously 4 times within 20 minutes, timer LED will be blinking (“F96” is indicated).

šDC Peak Current Control

1When electric current to IPM exceeds set value of 16.0 ±2.0A, the compressor will stop operate. Then, operation will restart after 3 minutes.

2If the set value is exceeded again more than 30 seconds after the compressor starts, the operation will restart after 1 minute.

3If the set value exceeded again within 30 seconds after the compressor starts, the operation will restart after 1 minute. If this condition repeats continuously for 7 times, all indoor and outdoor relays will be cut off, timer LED will be blinking (“F99” is indicated).

44

Image 44
Contents Air Conditioner CU-XE12PKUATable of Contents Safety Precautions š The items to be followed are classified by the symbolsPage Specifications CU-XE9PKUASeer / Hspf CS-XE9PKUA CU-XE9PKUA CS-XE12PKUA CU-XE12PKUA CS-XE12PKUA Pipe Diameter Liquid / Gas Mm inch Features š Inverter TechnologyIndoor Unit Outdoor Unit Remote Control Location of Controls and ComponentsDimensions Indoor UnitOutdoor Unit Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Model CU-XE9/12PK Connection Electronic Circuit Diagram Outdoor Unit Main Printed Circuit Board Indicator Printed Circuit Board Printed Circuit BoardPage Main Printed Circuit Board Installation Instruction Indoor/Outdoor Unit Installation DiagramSelect the Best Location Indoor UnitTo Drill a Hole in the Wall and Install a Sleeve of Piping Indoor Unit Installation Page Connect the Cable to the Indoor Unit Install the Outdoor Unit Connect the PipingEvacuation of the Equipment Connect the Cable to the Outdoor UnitPiping Insulation Cutting and flaring the pipingOperation Control Basic FunctionIndoor Fan Motor Operation Automatic OperationFan Operation Basic Rotation Speed rpmOutdoor Fan Motor Operation Feedback controlAirflow Direction Vertical AirflowHorizontal Airflow Quiet operation Cooling Mode/Cooling area of Dry ModeQuiet Operation Heating Powerful Mode Operation Timer ControlAuto Restart Control Indication PanelRoom Freeze Protection Function RFP Operation Auto Comfort and Econavi OperationHuman Activity Sensor Information Log Rhythmic Temperature Wave Operation Econavi and Auto Comfort Demo Mode Human Activity Sensor Check Mode Restart Control Time Delay Safety Control IPM Power transistor Prevention ControlProtection Control Protection Control For All OperationsLow Frequency Protection Control Compressor Overheating Prevention ControlLow Pressure Prevention Control Gas Leakage Detection Outdoor Air Temperature Control Protection Control For Cooling & Soft Dry OperationCooling Overload Control Freeze Prevention ControlProtection Control For Heating Operation Servicing Mode Auto OFF/ON ButtonRemote Control Button Reset RCReset AC TimerTroubleshooting Guide Refrigeration Cycle SystemCondition Cooling Mode Heating Mode To Display Memorized Error Code Protective Operation Breakdown Self Diagnosis FunctionSelf Diagnosis Function Three Digits Alphanumeric Code To Make a DiagnosisError Codes Table Protection controlDiagnosis Abnormality Protection Problem Self-diagnosis Method 15.4.1 H11 Indoor/Outdoor Abnormal Communication15.4.2 H12 Indoor/Outdoor Capacity Rank Mismatched 15.4.3 H14 Indoor Intake Air Temperature Sensor Abnormality 15.4.4 H15 Compressor Temperature Sensor Abnormality 15.4.5 H16 Outdoor Current Transformer 15.4.6 H19 Indoor Fan Motor DC Motor Mechanism Locked 15.4.7 H23 / H24 Indoor Pipe Temperature Sensor Abnormality 15.4.8 H27 Outdoor Air Temperature Sensor Abnormality 15.4.9 H28 Outdoor Pipe Temperature Sensor Abnormality Malfunction Decision Conditions Malfunction Decision Conditions 15.4.12 H33 Unspecified Voltage between Indoor and Outdoor 15.4.13 H36 Outdoor Gas Pipe Sensor Abnormality Malfunction Decision Conditions 15.4.15 H97 Outdoor Fan Motor DC Motor Mechanism Locked Malfunction Decision Conditions Malfunction Caused 15.4.18 F11 4-way Valve Switching Failure 15.4.19 F17 Indoor Standby Units Freezing Abnormality Remark15.4.20 F90 Power Factor Correction Protection 15.4.21 F91 Refrigeration Cycle Abnormality 15.4.22 F93 Compressor Rotation Failure Malfunction Decision Conditions 15.4.24 F96 IPM Overheating Multi Models only15.4.25 F97 Compressor Overheating 15.4.26 F98 Input Over Current Detection 15.4.27 F99 DC Peak Detection Disassembly and Assembly Instructions To remove front grille To remove electronic controllerTo remove discharge grille Page Page Page Outdoor Electronic Controller Removal Procedure Technical Data Operation CharacteristicsPage Page Page CS-XE12PKUA CU-XE12PKUA Page Page Page Sensible Capacity Chart š CU-XE9PKUAExploded View and Replacement Parts List CS-XE9PKUA CS-XE12PKUARemark BAG Outdoor Unit 101 Shock Absorber Right