4

 

 

4.2Set-up of Equipment

To prepare the ice bath:

a)Fill a glass beaker with crushed ice made from distilled water.

b)Fill the beaker with enough distilled water so that ice just becomes slush, but not enough to float the ice.

c)Insert the reference thermocouple.

Figure 4-2 shows an alternate set-up. Here, a high precision thermocouple calibrator, such the OMEGA Model CL511, replaces the DVM, ice bath, voltage source, etc.

18

Image 23
Contents User’sGuide Servicing North America Return Requests / Inquiries Introduction Calibration Instructions General Description IntroductionIntroduction TX91 Thermocouple Transmitter Introduction Introduction Straight line Approximation of Curve Models Available FeaturesTX91 Models Available Model Number Description Unpacking Mounting the TX91 InstallationAssembly of the TX91 Transmitter Inside RT Mounting Track in inches TX90-BR Mounting Bracket in inches Mounting Track RT Bracket TX90-BR Wiring the TX91 Refer to Figure Wiring Diagram for the TX91 Potentiometers Equipment Required Calibration InstructionsSet-up of Equipment Calibration Procedures Refer to Figure Calibration Instructions Calibration Set-Up Calibration Set-Up. Alternate Calibration Values for the TX92 Current rating on the power supply Troubleshooting GuideTroubleshooting Guide Model No Description AccessoriesGeneral SpecificationsInput Intrinsically Safe Interconnection Diagram WARRANTY/DISCLAIMER Shop online at omega.com