Table 3 Ð 19XB Storage Tank Rated Dry Weight and Refrigerant Capacity
English
|
|
| TANK OD |
| DRY WEIGHT* |
| MAXIMUM REFRIGERANT CAPACITY (lb) |
| |||
SIZE CODE |
| ASHRAE/ANSI 15 | UL 1963 |
| |||||||
(in.) |
| (lb) |
| ||||||||
|
|
|
|
|
|
|
| ||||
| 0428 |
| 24.00 |
| 2380 | 1842 |
| 1860 | 1704 |
| 1716 |
| 0452 |
| 27.25 |
| 3460 | 3527 |
| 3563 | 3264 |
| 3286 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SI |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TANK OD |
| DRY WEIGHT* |
| MAXIMUM REFRIGERANT CAPACITY (kg) |
| |||
SIZE CODE |
| ASHRAE/ANSI 15 | UL 1963 |
| |||||||
(mm) |
| (kg) |
| ||||||||
|
|
|
|
|
|
|
| ||||
| 0428 |
| 610 |
| 1080 | 836 |
| 844 | 773 |
| 778 |
| 0452 |
| 592 |
| 1569 | 1600 |
| 1616 | 1481 |
| 1491 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LEGEND |
|
|
|
|
|
|
| |
ANSI | Ð | American National Standards Institute |
|
|
|
|
|
| |||
ASHRAE Ð American Society of Heating, Refrigeration, |
|
|
|
|
|
| |||||
|
| and Air Conditioning Engineers |
|
|
|
|
|
|
| ||
UL | Ð Underwriters' Laboratories |
|
|
|
|
|
|
|
*The above dry weight includes the pumpout unit weight of 210 lbs (95 kg).
Make Piping Connections Ð Figure 6 represents typi- cal pumpout unit/chiller piping connections. Standard con- nections for
NOTE: If any ®eld piping runs exceed 50 ft in length, use
Pumpout unit water piping connections are shown in Fig. 6. Both connections are
INSTALL VENT PIPING TO RELIEF DEVICES Ð The pumpout storage tank is
Refrigerant discharged into con®ned spaces can dis- place oxygen and cause asphyxiation.
1.If relief devices are manifolded, the
2.Provide a pipe plug near outlet side of each relief device for leak testing. Provide pipe ®ttings that allow vent pip- ing to be disconnected periodically for inspection of valve mechanism.
3.Piping to relief devices must not apply stress to the de- vice. Adequately support piping. A length of ¯exible tub- ing or piping near the device is essential on spring- isolated machines.
4.Cover the outdoor vent with a rain cap and place a con- densation drain at the low point in the vent piping to pre- vent water
Make Electrical Connections Ð See nameplate on compressor of pumpout unit and Table 1 for motor electrical data. Wire unit according to the diagram inside the control box.
Fig. 7 is the wiring schematic for a complete system that includes the 19XB storage tank and the pumpout unit. Fig. 8 is the wiring schematic for the pumpout unit. Use this schematic for installations that do not include an auxiliary pumpout storage tank.
NOTE: Use copper conductors only.
7