Carrier 19XB Storage Tank Rated Dry Weight and Refrigerant Capacity, Tank OD DRY Weight, Ansi

Page 7

Table 3 Ð 19XB Storage Tank Rated Dry Weight and Refrigerant Capacity

English

 

 

 

TANK OD

 

DRY WEIGHT*

 

MAXIMUM REFRIGERANT CAPACITY (lb)

 

SIZE CODE

 

ASHRAE/ANSI 15

UL 1963

 

(in.)

 

(lb)

 

 

 

 

 

 

 

R-22

 

R-134a

R-22

 

R-134a

 

0428

 

24.00

 

2380

1842

 

1860

1704

 

1716

 

0452

 

27.25

 

3460

3527

 

3563

3264

 

3286

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TANK OD

 

DRY WEIGHT*

 

MAXIMUM REFRIGERANT CAPACITY (kg)

 

SIZE CODE

 

ASHRAE/ANSI 15

UL 1963

 

(mm)

 

(kg)

 

 

 

 

 

 

 

R-22

 

R-134a

R-22

 

R-134a

 

0428

 

610

 

1080

836

 

844

773

 

778

 

0452

 

592

 

1569

1600

 

1616

1481

 

1491

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

 

 

 

 

ANSI

Ð

American National Standards Institute

 

 

 

 

 

 

ASHRAE Ð American Society of Heating, Refrigeration,

 

 

 

 

 

 

 

 

and Air Conditioning Engineers

 

 

 

 

 

 

 

UL

Ð Underwriters' Laboratories

 

 

 

 

 

 

 

*The above dry weight includes the pumpout unit weight of 210 lbs (95 kg).

Make Piping Connections Ð Figure 6 represents typi- cal pumpout unit/chiller piping connections. Standard con- nections for 1¤2-in. OD copper tubing are provided. Install the ®eld-supplied FPT tee with pipe plug in the piping as shown in Fig. 6. This tee is used for refrigerant charging.

NOTE: If any ®eld piping runs exceed 50 ft in length, use 7¤8-in. OD copper tubing to minimize pressure drop.

Pumpout unit water piping connections are shown in Fig. 6. Both connections are 1¤2-in. NPT (female). A shutoff valve should be installed in the water line. Provide a means for blowing water from the condenser coil at winter shut- down to prevent freeze-up damage. Refer to the Job Data for water piping particulars.

INSTALL VENT PIPING TO RELIEF DEVICES Ð The pumpout storage tank is factory-equipped with relief de- vices. Refer to Fig. 5 and Table 2 for size and location of the relief devices. Vent the relief devices to the outdoors in ac- cordance with ANSI/ASHRAE 15 Safety Code (latest edi- tion) for Mechanical Refrigeration and all other applicable codes. Relief devices are set to relieve at 300 psig (2068 kPa).

Refrigerant discharged into con®ned spaces can dis- place oxygen and cause asphyxiation.

1.If relief devices are manifolded, the cross-sectional area of the relief pipe must at least equal the sum of the areas required for individual relief pipes.

2.Provide a pipe plug near outlet side of each relief device for leak testing. Provide pipe ®ttings that allow vent pip- ing to be disconnected periodically for inspection of valve mechanism.

3.Piping to relief devices must not apply stress to the de- vice. Adequately support piping. A length of ¯exible tub- ing or piping near the device is essential on spring- isolated machines.

4.Cover the outdoor vent with a rain cap and place a con- densation drain at the low point in the vent piping to pre- vent water build-up on the atmospheric side of the relief device.

Make Electrical Connections Ð See nameplate on compressor of pumpout unit and Table 1 for motor electrical data. Wire unit according to the diagram inside the control box.

Fig. 7 is the wiring schematic for a complete system that includes the 19XB storage tank and the pumpout unit. Fig. 8 is the wiring schematic for the pumpout unit. Use this schematic for installations that do not include an auxiliary pumpout storage tank.

NOTE: Use copper conductors only.

7

Image 7
Contents Safety Considerations Installation, Operating, and Maintenance InstructionsInstallation ContentsIntroduction Refrigerant LRA Assembly no Positive Pressure System Assembly NumbersRLA Tank Number 19XB Positive Pressure Storage System Trade Size QTY Location 19EA Pumpout Unit Typical Chiller MountTank Size Storage Center of Gravity Empty WeightEnglish Size Code ASHRAE/ANSI 19XB Storage Tank Rated Dry Weight and Refrigerant CapacityTank OD DRY Weight Maximum Refrigerant Capacity lbTrade QTY Location Size PPS Contact Surface and DimensionsRefrigerant Transfer Connections Condenser Water Cooling ConnectorsConnection SizeRelief Devices Operation High Condition Pressure Switch SettingsRefrigerant HIGH-PRESSURE Switch Controls and ComponentsValve Condition Pumpout UnitValve Locations for 19XB Pumpout Unit With 19XB Storage Tank Valve Locations for 19XB Pumpout Unit Without Storage Tank Freeze-up Leak test to ensure chiller vessel integrity MaintenanceSymptom Probable Cause Remedy TroubleshootingTroubleshooting ISO Carrier Refrigerant Specification