Carrier Comprehensive Chiller Schematic and General Piping Connection Sizes

Page 9

CHILLERS WITHOUT ISOLATION VALVES

CHILLERS WITH ISOLATION VALVES

 

(WITH OR WITHOUT PUMPOUT STORAGE TANKS)

GENERAL PIPING CONNECTION SIZES

CONNECTION

 

SIZE (in.)

Refrigerant Transfer Connections

1¤2

ODS (female)

Condenser Water Cooling Connectors

1¤2

NPT (female)

Safety Relief Head Pumpdown Condenser

3¤8

Flare (male)

ODS Ð Outside Diameter, Sweat

NOTES:

1.The ®eld-supplied tubing is to be1¤2-in. OD tubing (min.) and must be arranged and supported to avoid stresses on the equipment, transmission of vibrations, and interference with routine access during the reading, adjusting, and servicing of the equipment. If the distance from the chiller to the pumpout unit is over 50 ft, then 7¤8-in. OD tubing (min.) must be used. Provisions should be made for adjustment in each plane of the tubing and for both periodic and major servicing of the equipment. Special care must be taken so that the safety head does not experience tubing strain. Vent the safety head per ASHRAE 15 (American Society of Heating, Refrigeration, and Air Conditioning Engineers), latest revision.

2.The tubing and valve from the storage tank to the pumpout com- pressor is factory supplied when the unit is factory mounted.

LEGEND

Factory-Supplied Tubing

Field-Supplied Tubing

Field-Supplied Tubing (Multiple Chillers)

Service Valve (Factory Supplied)

Service Valve (Field Supplied)

Fig. 6 Ð Typical Pumpout Unit/Chiller Connection Schematic

9

Image 9
Contents Safety Considerations Installation, Operating, and Maintenance InstructionsContents InstallationIntroduction Positive Pressure System Assembly Numbers Refrigerant LRA Assembly noRLA Tank Number 19XB Positive Pressure Storage System Trade Size QTY Location 19EA Pumpout Unit Typical Chiller MountStorage Center of Gravity Empty Weight Tank SizeEnglish Tank OD DRY Weight 19XB Storage Tank Rated Dry Weight and Refrigerant CapacityMaximum Refrigerant Capacity lb Size Code ASHRAE/ANSITrade QTY Location Size PPS Contact Surface and DimensionsConnection Condenser Water Cooling ConnectorsSize Refrigerant Transfer ConnectionsRelief Devices Refrigerant HIGH-PRESSURE Switch High Condition Pressure Switch SettingsControls and Components OperationValve Condition Pumpout UnitValve Locations for 19XB Pumpout Unit With 19XB Storage Tank Valve Locations for 19XB Pumpout Unit Without Storage Tank Freeze-up Leak test to ensure chiller vessel integrity MaintenanceTroubleshooting TroubleshootingISO Carrier Refrigerant Specification Symptom Probable Cause Remedy