| Installation, Operation & Maintenance Manual |
MSP900SH | IP2040/IM, Rev. AA |
May 2007 | |
|
|
Appendix 2 - Use with Mobrey Measurement MSP90 Series controllers – example
Programming example when using the new MSP900SH transmitter with an old style MSP90 Series controller.
A2.1 Vertical rectangular or cylindrical sump, originally displaying level in metres, 4.2m from transducer face to bottom of sump.
•The new MSP900SH should be mounted in the same position as the old transducer such that the distance to the bottom of sump is 4.2m. If this is not possible,
•The MSP900SH transmitter should be configured with a bottom reference of 4.2m
(or whatever the new distance is) and the
If there is no HART device available to configure the MSP900SH in this way, refer to the note below.
•On the MSP90 control unit :
Set P39 | = 7 | (Current input) |
Set P3 | = 3.9 (Range of | |
Set or check P21 | = 0 | (linear vessel) |
Note : If it is not possible to
In this case, P3 must be set to 11.7 as this is the full range of the transmitter signal.
If in doubt, do not hesitate to contact Mobrey Measurement Customer Support for further advice.