CHECKOUT PROCEDURE

After installation has been completed, it is recommended that the entire system be checked against the following list:

1.

Refrigerant Line, Leak checked

[

]

2.

Suction Lines and Fittings properly insulated

[

]

3.

Have all Refrigerant Lines been secured and

 

 

 

isolated properly?

[

]

4.Have passages through masonry been sealed? If mortar is used, prevent mortar from coming

 

into direct contact with copper tubing

[

]

5.

Verify tightness of all electrical connects

[

]

6.

Observe outdoor fan during on cycle for clearance

 

 

 

and smooth operation

[

]

7.

Indoor coil drain line drains freely. Pour water

 

 

 

into drain pan

[

]

8.

Supply registers and return grilles open and

 

 

 

unobstructed

[

]

9.

Return air filter installed

[

]

10.Thermostat thermometer is accurate. Check against a reliable thermometer. Adjust per

 

instructions with thermostat

[

]

11.

Is correct speed tap being used?

 

 

 

(Indoor blower motor)

[

]

12.

Operate complete system in each mode to

 

 

 

insure safe operation

[

]

TROUBLESHOOTING CHART — WHAT TO CHECK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

REF

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

CONTROL

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

WHAT

HIGH

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEFROST

 

 

 

 

 

 

 

 

 

LOW

 

 

 

STUCK

REF

 

 

AIR

 

 

CIR

SOVCHECK

 

 

 

 

 

 

 

 

 

CONTACTOR

 

 

LOW

 

EXCESSIVE

RES

 

 

 

 

 

DEFROST

 

 

TO

 

 

 

 

 

 

 

 

 

REF

 

 

TXV

RES .

 

 

 

 

 

 

 

START

 

 

 

 

 

 

 

.

 

 

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

 

 

 

 

.

 

 

COIL

 

 

 

 

POWERVOLTAGE

RUN

 

 

VOLTAGE

 

 

 

INEFFICIENT

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

 

 

VALVE

 

 

 

 

 

 

CONTACTOR

 

 

 

.

 

 

 

.

 

SOV

 

 

SYSTEM FAULTS CHECK COMPRESSOR

START

 

 

 

 

VOLTAGE

 

 

 

.

 

 

.

 

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONCONDENSABLESSTUCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

EVAP

RECIRCULATIONRESTRICTIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

UNDERCHARGE.

RELAY

 

 

 

 

 

 

 

 

 

 

 

THERMOSTATCOMPRESSOROVERCHARGE

 

 

SUPERHEAT

 

DEFECTIVE

 

 

 

 

 

 

CAPACITORCAPACITORCONTACTS

 

 

 

 

 

 

 

AIRFLOW

 

 

 

 

 

SUPPLYWIRING

 

 

RELAY

WIRING

 

 

FUSE COMP

 

 

 

AIRFLOWLEAKINGLEAKING

 

 

 

MODE

 

IOL

 

 

 

 

 

LOAD

 

 

OPEN

 

 

 

 

 

DEFDEF

 

 

 

 

 

 

 

 

 

 

 

COIL

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

. .

REFRIGERANT CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Head Pressure Too High

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

P

S

P

S

 

 

 

S

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

P

S

 

 

 

 

P

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Head Pressure Too Low

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

 

 

 

S

S

 

S

S

S

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

 

 

 

S

S

 

S

S

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Pressure Too High

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

P

 

 

 

 

S

 

 

P

 

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

 

 

S

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Pressure Too Low

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

S

P

S

 

S

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Refrig. Floodback (TXV)

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

P

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid Refrig. Floodback

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

S

S

 

S

P

 

 

 

 

 

(Cap. Tube)

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

S

S

 

S

 

 

 

S

 

 

I.D. Coil Frosting

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Runs

 

 

C

 

 

 

 

 

 

 

 

 

 

 

S

P

 

S

S

 

 

 

S

P

S

S

S

S

 

Inadequate or No Cooling/Htg

 

H

 

 

 

 

 

 

 

 

 

 

 

S

P

 

 

S

 

 

 

S

P

S

S

 

S

 

ELECTRICAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor & O.D. Fan

 

C

P

P

 

 

 

 

 

S

P

S

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Won’t Start

 

 

H

P

P

 

 

 

 

 

S

P

S

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Will Not Start

 

C

 

P

S

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

But O.D. Fan Runs

 

 

H

 

P

S

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O.D. Fan Won’t Start

 

C

 

P

 

P

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

P

 

P

 

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Hums But Won’t Start

 

C

 

 

 

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

P

S

S

S

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Cycles on IOL

 

C

 

P S P S S S

 

 

 

 

P S P P S

 

S S

 

S

 

 

S

 

 

 

 

H

 

P S P S S S

 

 

 

 

P S P P S

 

S

 

 

S P

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I.D. Blower Won’t Start

 

C

P

P

 

 

 

 

 

S

P

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

P

P

 

 

 

 

 

S

P

S

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEFROST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Won’t Initiate

Defrost

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

P

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost Terminates on Time

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Icing Up

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

P

 

 

 

S

S

 

 

S

 

 

P

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C - Cooling

H - Heating

P - Primary Causes

 

S - Secondary Causes

* - 3 Phase Only

 

 

 

 

 

 

 

 

 

 

 

Literature Order Number

2TWA2-IN-1A

P.I.

 

 

 

File Number

SV-UN-S/S-2TWA2-IN-1A 9/02

 

 

 

 

 

 

 

 

 

 

Supersedes

2TWA2-IN-1 4/02

 

 

 

 

 

 

 

 

 

 

Stocking Location

PI Louisville & Webb/Mason - Houston

 

Trane

 

 

 

 

 

 

A business of

Trane has a policy of continuous product and product data improvement and it reserves the right to change

 

American Standard Companies

 

www.trane.com

design and specifications without notice.

 

Image 8
Contents FT. Above UNIT-UNRESTRICTED GeneralLocation and Preparation of the Unit Installing Refrigerant Lines Liquid Line Service ValveAccutron Flow Control Valve Basepan TAB RemovalGAS Line Service Valve Service Valve OperationGAS Line Ball Service Valve Fault Identification Defrost ControlElectrical Connections PIN IdentificationOperational and Checkout Procedures Typical Field HOOK-UP DiagramsCompressor Start UP Electric Heaters2TWA Outline Drawing Models BaseMounting Hole Location Checkout Procedure Troubleshooting Chart What to Check