Trane 4TWB4 Heat Pump Specs and Accessories: Bayseac001 Insights

Page 4

General

Data

Product Specifications

Model No. 1

4TWB4018G1

4TWB4024G1

4TWB4030G1

4TWB4036G1

Electrical Data V/Ph/Hz 2

208/230/1/60

208/230/1/60

208/230/1/60

208/230/1/60

Min Cir Ampacity

9

11

15

18

Max Fuse Size (Amps)

15

15

25

30

Compressors

CLIMATUFF®

CLIMATUFF®

CLIMATUFF®

CLIMATUFF®

RL AMPS - LR AMPS

6.4 - 38.6

8.3 - 58

11.3 - 68.2

13.2 - 63

Outdoor Fan FL Amps

0.70

0.74

0.92

1.00

Fan HP

1/8

1/8

1/5

1/5

Fan Dia (inches)

23

23

27.5

27.5

Coil

Spine Fin™

Spine Fin™

Spine Fin™

Spine Fin™

Refrigerant R-410A

5/14-LB/OZ

7/02-LB/OZ

8/02-LB/OZ

7/13-LB/OZ

Line Size - (in.) O.D. Gas 3

5/8

5/8

3/4

3/4

Line Size - (in.) O.D. Liquid 3

3/8

3/8

3/8

3/8

Dimensions H x W x D (Crated)

34 x 30.1 x 33

38 x 30.1 x 33

38.4 x 35.1 x 38.7

37.9 x 35 x 37.9

Weight - Shipping

204

236

273

261

Weight - Net

176

208

239

227

Start Components

YES

YES

YES

YES

Sound Enclosure

NO

NO

NO

YES

Compressor Sump Heat

NO

NO

NO

NO

Optional Accessories: 4

 

 

 

 

Anti-short Cycle Timer

TAYASCT501A

TAYASCT501A

TAYASCT501A

TAYASCT501A

Evaporator Defrost Control A/C

AY28X084

AY28X084

AY28X084

AY28X084

Rubber Isolator Kit

BAYISLT101

BAYISLT101

BAYISLT101

BAYISLT101

Crankcase Heater

BAYCCHT300

BAYCCHT300

BAYCCHT300

BAYCCHT300

Extreme Condition Mounting Kit

BAYECMT004

BAYECMT004

BAYECMT004

BAYECMT004

Snow Leg - Base & Cap 4" High

BAYLEGS002

BAYLEGS002

BAYLEGS002

BAYLEGS002

Snow Leg - 4" Extension

BAYLEGS003

BAYLEGS003

BAYLEGS003

BAYLEGS003

Seacoast Kit

BAYSEAC001

BAYSEAC001

BAYSEAC001

BAYSEAC001

Refrigerant Lineset 5

TAYREFLN950

TAYREFLN950

TAYREFLN7*

TAYREFLN7*

 

 

 

 

 

1Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification program which is based on AHRI Standard 210/240.

2 Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.

3 Standard line lengths - 80'. Standard lift - 60' Suction and Liquid line.

For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0. (denotes latest revision)

4 For accessory description and usage, see page 5.

5 * = 15, 20, 25, 30, 40 and 50 foot lineset available.

A-weighted Sound Power Level [dB(A)]

 

 

 

 

 

 

 

 

 

 

MODEL

SOUND POWER

A-WEIGHTED FULL OCTAVE SOUND POWER LEVEL dB - [dB(A)] High Stage

 

LEVEL [dB(A)]

63

125

250

500

1000

2000

4000

8000

 

 

 

4TWB4018G

76

52.3

57.8

62.4

67.2

69.4

67.2

59.6

52.5

 

 

 

 

 

 

 

 

 

 

 

 

4TWB4024G

76

50.3

55

58.6

65.3

69.5

64.5

58.6

50.8

 

 

 

 

 

 

 

 

 

 

 

 

4TWB4030G

76

48.8

55.4

60.1

66.4

67.4

63.9

60.2

53.5

 

 

 

 

 

 

 

 

 

 

 

 

4TWB4036G

76

54.5

55.1

58.3

67

69.8

65.9

59.7

49.1

 

 

 

 

 

 

 

 

 

 

 

 

4TWB4042E

78

55.1

52

59.3

64.9

67.2

63.5

60.4

47.6

 

 

 

 

 

 

 

 

 

 

 

 

4TWB4048E

78

55.6

53.3

59.2

66.7

71.7

67.9

60.7

51.3

 

 

 

 

 

 

 

 

 

 

 

 

4TWB4049E

76

43.7

51.2

54.5

61

61.5

57.1

51.3

40.7

 

 

 

 

 

 

 

 

 

 

 

 

4TWB4060E

78

55.1

53.7

61.1

69.2

73.6

68.7

61.4

50

 

 

 

 

 

 

 

 

 

 

 

 

4TWB4061E

76

31.9

58.9

57.1

64.8

66.4

59.8

55.9

51.2

 

 

 

 

 

 

 

 

 

 

 

 

Note: Rated in

accordance with AHRI

Standard 270-2008.

4

 

 

 

 

22-1834-09

Image 4
Contents Split System Heat Pump Product Data Features and Benefits Weatherguard fastenersContents Product Specifications General DataSound Enclosure Compressor Sump Heat Ahri Standard 210/240 Rating Conditions Model Nomenclature Outdoor UnitsSchematic Diagrams 4TWB4018, 4TWB4024, 4TWB4036 Electrical DataSchematic Diagrams 4TWB4030 Schematic Diagrams 4TWB4042 Schematic Diagrams 4TWB4048 Schematic Diagrams 4TWB4049ESchematic Diagrams 4TWB4060 4TWB4061E Dimensions 4TWB4 Outline DrawingMechanical Specification Options General