Schneider Electric 9070 manual Multiple Secondary, Amps

Page 19

Industrial Control Transformers

Multiple Secondary

MULTIPLE SECONDARY

Designed to meet the needs for both 24 V control and 120 V control. Available in the 9070 Type T product line, with all the type T features.

Tapped Secondary D15: 24 V rated for 20% capacity and 120 V rated for 80% capacity when simultaneous loading, or 100% loading when 120 V only.

20% rating at 24 V or 100% rating at 120 V gives equal output current from the device.

VA

24 V amps

120 V amps

 

 

 

50

.416

.416

 

 

 

75

.625

.625

 

 

 

100

.833

.833

 

 

 

150

1.25

1.25

 

 

 

200

1.67

1.67

 

 

 

250

2.08

2.08

 

 

 

300

2.5

2.5

 

 

 

350

2.9

2.9

 

 

 

500

4.17

4.17

 

 

 

750

6.25

6.25

 

 

 

1000

8.3

8.3

 

 

 

1500

12.5

12.5

 

 

 

2000

16.7

16.7

 

 

 

3000

25

25

 

 

 

5000

41.7

41.7

 

 

 

Tapped Secondary D65: Both outputs fully rated for non-simultaneous loading, and simultaneous rated for any combination that does not exceed the nameplate VA rating.

Separate Windings Options: All voltage codes offer fully rated non-simultaneous loading, and simultaneous rated for any combination that does not exceed the nameplate VA rating.

Features of separate windings:

1.Allows two isolated control circuits, 24 V and 120 V, from the same device

2.Wire sizing for circuits for each voltage not highest current for common when simultaneous loading. (no common)

3.If a common is required, it can be obtained with a jumper kit.

19

08/2005

 

 

 

© 1999–2005 Schneider Electric All Rights Reserved

Image 19
Contents Industrial Control Transformers Page Product Description Product DescriptionType T VA Ratings Type T TransformersType T Transformers CE Marking95% 90% 85% Regulation Chart for Type TSelection Guide Secondary VoltageSource Load Voltage Go To Codes Pages Type T Transformers for 120 Volt LoadsSingle Dual Custom-Built Type T TransformersType T Transformers for 24 Volt Loads One Primary Tap Two Primary TapsVoltages DimensionsVolt Control Secondary Voltage and Connection OptionsVoltages Connections Key Type T MultiTap TransformersCatalog Acc Slots Number1 ConnectionsVoltage Voltages Connections Volt SecondaryPrimary Secondary UniversalCatalog Type T Transformers with Dual Secondary120/240 Volt Secondary Voltage VoltagesCatalog Acc Slots Number1 Key Catalog Acc Type T Transformers with 24 Volt SecondaryNumber1 Key 9070T50D19 Type T Units with Dual 12/24 Volt Secondary Multiple Secondary Multiple SecondaryAmps 120 Type T Units with Dual 24/120 Volt Secondary Tapped UnitsOnly Acc 115Slots Only Catalog 115V 24V9070T50D114 B D a B 150 Exceed Primary Max 200 9070T200t 120 114 Load Type T Performance Data0PF 100% 75% 50% 25% 60HZ 50HZ WattsType T Special Quote Request Sheet Type EO VA Ratings Regulation Chart for Type EOType EO Transformers Type EO TransformersType EO Transformers for 24 Volt Loads Type EO Transformers for 120 Volt LoadsCatalog Slots Number Voltage Voltages Catalog Slots Number19070EO17 t Voltages Connections Inrush x FL RMS Type EO Performance DataCatalog Core Coil FL Total Reg Eff BTU/hr 0PF 100% 75% 50% 25% 60HZTransformers with Leads Transformers with LeadsClass 9070 Type EL, KL Fuse Protection Matrix for Choosing Proper Fuse ConfigurationFuse Protection H3 H2 X2X1 H1H4 H1H4 H3 H2 Fuse Protection Options Description of Accessory KeysFingersafe Covers not supplied with unit AccessoriesClass Type VA Accessory Key Description VA Accessory KeyVolts Primary Fusing to Meet NECVolts Volts Secondary Fuse Rating Primary Fusing to Meet CESecondary Fusing to Meet NEC and CE Recommended Fuse Sizes for the Secondary to Meet NEC and CEVolt Control Secondary-Primary and Secondary Fuse Block Type TF Transformers9070TF25D20 Field Installed Fuse Options Field Installed Fuse OptionsPrimary Fusing R01A R01B Primary and Secondary Fusing R11A R11B R12A R12B Secondary Fusing S22A S22B SF25A SF25B AP1 AP2 Secondary Fuse Clips Jumper Fuse ClipTerminal Blocks Application ApplicationExample of Series and Parallel Connections Example of a typical application SolutionTechnical Data Frequently Asked Questions Frequently Asked QuestionsQuestion Answer Selecting a 9070 Type T control transformer? Schneider Electric USA