3Com MS40-717X Wiring Requirements, Control and Power Leads, Control and Power Wiring Data

Page 14

AM-753

Universal

Mounting

Clamps

1

AM-676 Universal Shaft Extension

V-clamp

Duct

Actuator

Anti-rotation Bracket (included with actuator)

Mounting Surface

1The AM-676 extends the damper shaft approximately 9" (229 mm).

Damper Shaft

 

Figure-13 Installation of Universal Shaft Extension.

Wiring Requirements

Control and Power Leads

 

Remove blue plastic thread protectors before installing conduit fittings. See Figure-1through

 

Figure 8 for typical wiring applications and Table-3for maximum wire lengths.

 

 

 

Caution: The 24 Vac model contains a half-wave rectifier power supply and must not be

 

powered by transformers used to power other devices utilizing non-isolated full-wave

 

rectifier power supplies. Refer to EN-206 Guidelines for Powering Multiple Full-Wave and

 

Half-Wave Rectifier Devices from a Common Transformer, F-26363, for further information.

 

 

 

Note: Class 2 control and power lead wiring must be routed separately from line voltage

 

wiring and any other non-class 2 circuits.

 

 

Table-3 Control and Power Wiring Data.

Actuator

Part

Maximum Wire Run in ft. (m)

 

(5% Voltage Drop)

 

Voltage

Number

 

 

14 AWG

 

16 AWG

 

18 AWG

 

 

 

 

24 Vac and

MS40-7173

 

 

 

 

 

22-30 Vdc

981

 

617

 

388

 

 

 

120 Vac

MS40-7170

(299)

 

(188)

 

(118)

240 Vac

MS40-7171

 

 

 

 

 

Table-4 Wire Color Codes for Models Manufactured before December, 2007.

Part Number

Power

L1

L2

Ground

24 H

24 G

Analog

500 Ohms

Common

Voltage

Input

 

 

 

 

 

 

 

 

MS40-7173-0-0-0

24 Vac

N/A

N/A

Green/Yellow

Black

Black/Blue

White

Red

Black

Old Design

 

 

 

 

 

 

 

 

 

MS40-7170-0-0-0

120 Vac

Black

White

Green/Yellow

N/A

N/A

White

Red

Black

Old Design

 

 

 

 

 

 

 

 

 

MS40-7171-0-0-0

240 Vac

Brown

Light

Green/Yellow

N/A

N/A

White

Red

Black

Old Design

 

 

Blue

 

 

 

 

 

 

N/A: Not Applicable

14

Copyright 2010 Schneider Electric All Rights Reserved.

F-26748-6

Image 14
Contents MS40-717X Series Inputs SpecificationsApplicable Literature OutputsEnvironment Ambient Temperature LimitsModel Chart Agency ListingsTypical Applications wiring diagrams GRDTypical MS40-7171 2 to 10 Vdc Wiring Diagram Power Wiring Identification Voltage Designation Wire ColorRequirements InstallationInspection Federal Communications Commission FCC PrecautionsGeneralLocationCaution Canadian Department of Communications DOCDamper Actuator Sizing Steel Damper Shaft SpecificationsMounting Damper Shaft SizingLong Damper Shafts Centerline Mounting Anti-rotation Bracket to Actuator Short Damper Shafts Control and Power Wiring Data Wiring RequirementsControl and Power Leads Wire Color Codes for Models Manufactured before DecemberTheory of Operation MaintenanceCheckout Field RepairDimensional Data 10-27/32