3Com MS40-717X warranty Environment, Agency Listings, Minimum Damper Shaft Length, Model Chart

Page 3

Minimum Damper Shaft Length,

Standard Damper shaft must be at least 4-5/8" (117 mm) long for standard mounting. Optional Shorter than standard length shafts require the AM-676 shaft extension (order separately).

Position Indicator, Scale numbered from 0 to 95°, provided for position indication. Nominal Damper Area, Actuator sizing should be done in accordance with damper manufacturer’s specifications.

Direction of Rotation, Clockwise or counterclockwise rotation is determined by actuator mounting. The zero (0) position on the position indicator is the normal or spring return position.

Environment

Ambient Temperature Limits:

Shipping & Storage, -40 to 160°F (-40 to 71°C). Operating, -25 to 140°F (-32 to 60°C).

Humidity: 5 to 95% RH, non-condensing.

Location: NEMA 1. NEMA Type 4 (IEC IP56) with customer supplied water tight conduit connectors.

Agency Listings

UL 873: Underwriters Laboratories Inc. listed (File # E9429 Category Temperature- Indicating and Regulating Equipment).

CUL: UL Listed for use in Canada by Underwriters Laboratories. Canadian Standards C22.2 No. 24-93.

European Community: EMC Directive (2004/188/EC). Low Voltage Directive (72/23/EEC). See Table-1for specific models.

Australia: This product meets requirements to bear the C-Tick Mark according to the terms specified by the Communications Authority under the Radiocommunications Act 1992.

Table-1 Model Chart.

 

 

Actuator Power Input

 

Approximate 93° Rotation

Output Torque Rating

 

 

 

 

 

 

 

 

Timing in Seconds @ 70° F

Part

 

 

 

 

VA

 

lb.-in. (N-m)

 

 

 

Running

 

(21°C) for Rated Torque

Number

Voltage

Hz

 

 

 

 

 

Watts

Running

 

Holding

Powered

Spring

Minimum

Maximum Stall

 

 

 

 

 

 

 

 

 

 

 

Return

 

 

 

 

 

 

 

 

 

 

 

MS40-7173

24 Vac ±20%

50

60

5.5

7.8

 

4.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22-30 Vdc

 

 

5.0

5.6

 

2.5

147

65

150 (17)a

545 (61.8)

 

 

 

 

 

 

 

 

 

 

 

 

MS40-7170

120 Vac ±10%

50

60

6.4

8.5

 

5.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MS40-7171

240 Vac ±10%

7.2

10.8

 

9.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

aApproximate 2% torque derating per 1°F above 122°F in the drive direction.

ACCESSORIES

 

AM-620

Remote mount single/dual damper actuator kit

AM-621

Round damper shaft extension kit (1/2" ID x 1" OD) for dual actuator mounting

AM-703

Span adjustment

AM-704

Modulation Interface, converts a PWM to 2 to 10 Vdc

AM-705

Positioner, remote/minimum positioning

AM-706

Positioner, flush mount digital position indicator

AM-707

Digital Indication

AM-708

Resistor for 500Ω modulating signal conversion

AM-751

Standard anti-rotation bracket 9" long x 13/16" wide (229 x 21 mm), included with

 

actuator

AM-752

Optional anti-rotation bracket 4" long x 1-11/6" wide (102 x 43 mm), for narrow

 

spaces

AM-753

Optional universal mounting clamps for 5/8"(16 mm) square shaft, 3/4" and 1"

 

(19 to 25 mm) round shafts (two per package)

AM-754

Standard universal mounting clamps for 3/8" to 1/2" (10 to 13 mm) round and

 

square shafts, two included with actuator

AM-756

Metric conduit adaptor M20 x 1.5 to 1/2" NPT (two per package)

AV-607

Dual mount rack and pinion valve linkage kit for 2-1/2" through 5" VB-8xxx series

 

valve bodies and 2-1/2" to 4" VB-9xxx series valve bodies except VB-9323

AV-609

Dual mount rack and pinion valve linkage kit for 6" VB-8xxx series valve bodies and

 

5" and 6" VB-9xxx series valve bodies except VB-9323

TF-711-02

1/2" Sealtight water tight conduit connector (straight)

TF-713-02

1/2" Sealtight water tight conduit connector (90°)

X-5521

1/2" Pipe plug, included with actuator

F-26748-6

Copyright 2010 Schneider Electric All Rights Reserved.

3

Image 3
Contents MS40-717X Series Outputs SpecificationsApplicable Literature InputsAgency Listings Ambient Temperature LimitsModel Chart EnvironmentGRD Typical Applications wiring diagramsTypical MS40-7171 2 to 10 Vdc Wiring Diagram Voltage Designation Wire Color Power Wiring IdentificationInstallation InspectionRequirements Canadian Department of Communications DOC PrecautionsGeneralLocationCaution Federal Communications Commission FCCDamper Shaft Sizing Steel Damper Shaft SpecificationsMounting Damper Actuator SizingLong Damper Shafts Centerline Mounting Anti-rotation Bracket to Actuator Short Damper Shafts Wire Color Codes for Models Manufactured before December Wiring RequirementsControl and Power Leads Control and Power Wiring DataField Repair MaintenanceCheckout Theory of Operation10-27/32 Dimensional Data