321 Studios QW2S, QW5S warranty Energy Recovery Ventilator, Filter Options Select One

Page 4

The built-in commercial room ventilator (CRV) is internally mounted and allows outside ventilation air, up to 50% of the total air flow rating of the unit, to be introduced through the air inlet openings. The CRV shall be modular and easily added or removed from the unit cabinet. It includes a built-in exhaust air damper. The damper can be easily adjusted to control the amount of fresh air supplied into the building. The CRV can be controlled by indoor blower operation or field controlled based on room occupancy. Unit complies with ANSI/ASHRAE Standard 62.1 Ventilation for Acceptable Air Quality.

Two Models Available: Spring Return on Power Loss or Deactivation - Vent Option V

Power Return (will not close on power loss)

– Vent Option P

4.4 ENERGY RECOVERY VENTILATOR

OPTIONAL

The Energy Recovery Ventilator (ERV) shall consist of 1 or 2 rotary wheels in an insulated cassette frame with seals, drive motor and belt. The ERV assembly shall also include intake and exhaust blowers. The entire assembly shall easily slide in or out of the unit cabinet, allowing for maintenance or replacement. The total energy wheel shall be coated with silica gel desiccant, permanently bonded without the use of binders or adhesives. The coated segments shall be washable with detergent or alkaline coil cleaner and water. Desiccant shall not dissolve or deliquesce in the presence of water or high humidity. All diameter and perimeter seals shall be provided as part of the cassette assembly and shall be factory set. Drive belts shall not require external tensioners or adjustment. Cassette wheels shall include rims to prevent belts from slipping off wheels. Intake and exhaust blowers shall have selections of high, medium or low speed and selected independently, to allow for positive pressurization if desired. The ERV cassette including parts and media shall include 5year warranty subject to terms and conditions of Bard’s warranty.

The ERV thermal performance shall be certified by the manufacturer in accordance with ASHRAE Standard 84, Method of Testing Air-to Air Heat Exchangers and ARI Standard 1060, Rating for Air-to-Air Energy Recovery Ventilation Equipment Cassettes, and shall be listed in the ARI Certified Products. Unit complies with ANSI/ASHRAE Standard 62.1 Ventilation for Acceptable Air Quality.

.

5.0FILTER OPTIONS - (Select One)

F1915 (2012 04)

Page 4 of 6

Image 4
Contents QW2S-QW5S Water-to-Air H/P Engineering Specification Guide Construction Features CabinetBard Manufacturing COMPANY, INC GeneralCompressor Coaxial Water CoilIndoor Blower Motor Electrical ComponentsService Features Loop Module Pumping SystemBarometric Fresh AIR Damper Blank OFF PlateEnergy Recovery Ventilator Filter Options Select OneHOT GAS REHEAT- Factory installed option Accessories Wall SleeveCabinet Color Select One Exterior LouverInstallation WarrantyAIR Distribution Select