Two Models Available: Spring Return on Power Loss or Deactivation - Vent Option V
Power Return (will not close on power loss)
– Vent Option P
4.4 ENERGY RECOVERY VENTILATOR | OPTIONAL |
The Energy Recovery Ventilator (ERV) shall consist of 1 or 2 rotary wheels in an insulated cassette frame with seals, drive motor and belt. The ERV assembly shall also include intake and exhaust blowers. The entire assembly shall easily slide in or out of the unit cabinet, allowing for maintenance or replacement. The total energy wheel shall be coated with silica gel desiccant, permanently bonded without the use of binders or adhesives. The coated segments shall be washable with detergent or alkaline coil cleaner and water. Desiccant shall not dissolve or deliquesce in the presence of water or high humidity. All diameter and perimeter seals shall be provided as part of the cassette assembly and shall be factory set. Drive belts shall not require external tensioners or adjustment. Cassette wheels shall include rims to prevent belts from slipping off wheels. Intake and exhaust blowers shall have selections of high, medium or low speed and selected independently, to allow for positive pressurization if desired. The ERV cassette including parts and media shall include 5year warranty subject to terms and conditions of Bard’s warranty.
The ERV thermal performance shall be certified by the manufacturer in accordance with ASHRAE Standard 84, Method of Testing
.
5.0FILTER OPTIONS - (Select One)
F1915 (2012 04) | Page 4 of 6 |