Confined Space
Alternative
Air Inlet
1 sq. in. per
4000 BTUH
Gable Vent to Outdoors
Install Above Insulation
Outlet Air
to the Attic 1 sq. in. per 4000 BTUH
Inlet Air from the Crawl Space
Open
Foundation
Vent
Alternative
Opening
Location
Confined
Space
1 sq. in. per
3000 BTUH
All Air From Outdoors - Using A Single Permanent Opening
FIGURE 8B.
Vent Pipe System
All Air From Outdoors: Inlet Air From Ventilated
Crawl Space/Outlet Air To Ventilated Attic
This water heater uses a
Confined Space
FIGURE 6.
Gable Vent to Outdoors
Install Above
Outlet Air to the Attic 1 sq. in. per 4000 BTUH
Inlet Air Duct 1 sq. in. per 4000 BTUH
water heater location or is ducted in from the outside (see “Combustion Air Supply and Ventilation”).
This water heater must be properly vented for the removal of exhaust gases to the outside atmosphere. Correct installation of the vent pipe system is mandatory for the proper and efficient operation of this water heater and is an important factor in the life of the unit.
The vent pipe must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA
IMPORTANT: The use of vent dampers is not
12” Max.
All Air from Outdoors Through Ventilated Attic
FIGURE 7.
recommended by the manufacturer of this water heater. Although some vent dampers are certified by CSA International, this certification applies to the vent damper device only and does not mean they are certified for use on this water heater.
Confined Space
1 sq. in. per
2000 BTUH
Outlet
Outdoor
Air Ducts
U.L. recognized fuel gas and carbon monoxide (CO) detectors are recommended in all applications and should be installed using the manufacturer’s instructions and local codes, rules, or regulations.
IMPORTANT: If you lack the necessary skills required to properly install this venting system, you should not proceed, but get help from a qualified technician.
Draft Hood Installation
Inlet
1 sq. in. per
2000 BTUH
All Air From Outdoors Using Horizontal Ducts
FIGURE 8A.
| Sheet Metal Screws (Four Provided) | |
| Legs | Draft Hood |
|
| |
|
| Legs |
Slot |
| Slot |
|
| Jacket Top |
Install The Draft Hood With The Four Screws Provided.
FIGURE 9
13