American Water Heater 317994-002 installation instructions Temperature and Pressure Relief Valve

Page 16
Pressure Reducing Valve with Bypass
Main Water Supply

Hot Water Outlet

Metal Drain

Pan 1-3/4”

Depth Max.

In a closed system use a thermal expansion tank

Cold Water

Inlet Valve

Cold Water Supply to Fixture

Temperature and Pressure (T&P)

Relief Valve (Optional Top T&P

Relief Valve Not Shown)

Massachusetts: Install a vacuum relief in cold water line per section 19 MGL 142

Discharge line

(Do Not Cap or Plug)

1“ Min.

Drain line 3/4”

ID Min.

 

Drain

6“ Min.

Closed System/Thermal Expansion

As water is heated, it expands (thermal expansion). In a closed system, the volume of water will grow. As the volume of water grows, there will be a corresponding increase in water pressure due to thermal expansion. Thermal expansion can cause premature tank failure (leakage). This type of failure is not covered under the limited warranty. Thermal expansion can also cause intermittent temperature-pressure relief valve operation: water discharged from the valve due to excessive pressure build

Typical water piping installation

FIGURE 13.

Mixed Water

To Fixtures

Unmixed

Hot Water

Cold Water

Inlet

Hot Water

Outlet

Mixing Valve

(Set To 1200 F)

Follow The Mixing Valve

Manufacturer’s Instructions

FIGURE 14.

Please note the following:

The system should be installed only with piping that is suitable for potable (drinkable) water such as copper, CPVC, or polybutylene. This water heater must not be installed using iron piping or PVC water piping.

Use only pumps, valves, or fittings that are compatible with potable water.

It is recommend that only full flow ball or gate valves are used in water piping installations. The use of valves that may cause excessive restriction to water flow is not recommended.

Use only 95/5 tin-antimony or other equivalent solder. Any lead based solder must not be used.

Piping that has been treated with chromates, boiler seal, or other chemicals must not be used.

Chemicals that may contaminate the potable water supply must not be added to the piping system.

up. The temperature-pressure relief valve is not intended for the constant relief of thermal expansion. This condition is not covered under the limited warranty.

A properly-sized thermal expansion tank should be installed on all closed systems to control the harmful effects of thermal expansion. Contact a plumbing service agency or your retail supplier regarding the installation of a thermal expansion tank.

Temperature and Pressure Relief Valve

Explosion Hazard

Temperature-pressure relief valve must comply with ANSI Z21.22-CSA 4.4 and ASME code.

• Properly sized temperature- pressure relief valve must be installed in opening provided.

• Can result in overheating and excessive tank pressure.

• Can cause serious injury or death.

Temperature and

Pressure Relief Valve

(T&P)

Discharge line 3/4” Min.

Do not cap or plug.

Metal Drain Pan

6” Max.

Drain

FIGURE 15A.

16

Image 16
Contents Residential GAS Water Heaters Table of Contents Safe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Hazard Typical Installation GET to Know Your Water Heater GAS ModelsInstalling Your GAS Water Heater Unpacking the Water Heater Excessive Weight HazardImportant Information About This Water Heater Consumer InformationSite Location Location RequirementsCarbon Monoxide Poisoning Hazard Clearances and Accessibility State of CaliforniaGas Pressure Testing GAS SupplyGas Requirements Gas PipingGas Pipe Capacity Table Combustion AIR & Ventilation Unconfined SpaceConfined Space Minimum Btuh InputAll Air from Outdoors All Air from Inside the BuildingLouvers and Grilles Draft Hood Installation Vent Pipe SystemVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionTemperature & Pressure Relief Valve Relief Valve and Pipe InsulationCombination Space Heating/Potable Water System Discharge LineWiring Diagram Solar InstallationElectrical Connections Installation Checklist Important Information about this Water HeaterOperating Your Water Heater Operating InstructionsChecking the Draft Water Heater OperationBurn Hazard Burner Flames Water Temperature RegulationEmergency Shut Down Safety Shut-off Operational ConditionsCondensation Water Heater SoundsPowered Anode Operation Routine Preventive MaintenanceDraining and Flushing Maintenance of Your Water Heater Replacement PartsRemoving the Manifold/Burner Assembly Removing the Burner from the Manifold/ Burner AssemblyCleaning the Combustion Chamber and Air Diverter Assembly Replacing the Flame Sense/Hot Surface igniter AssemblyReplacing the Manifold/Burner Assembly Removing the Gas Control Valve/Thermostat Removing and Replacing the Gas Control Valve/ThermostatReplacing the Gas Valve Pressurized Combustion Chamber System Operational Checklist Troubleshooting ChartCont Control Display Troubleshooting Control Display Status Problem SolutionControl Display Status Problem Solution FV-SENSE and Open Flashing Troubleshooting Flowchart YESRepair Parts List Repair Parts IllustrationListed Parts Kits and Illustrations