Haier AD42NAHBEA, AD242AHBEA, AD52NAHBEA Chosen chart of simple duct, M3/hm3/n Mmxmm

Page 18

Installation Manual For Indoor Unit

The length difference among every duct is limited below 2:1.

Reduce the length of duct as possible as can.

Reduce the amount of bend as possible as can.

Use heat insulation material to bind and seal the part connecting main unit and the flare part of air discharging duct. Perform duct installation work, before the fitment of ceiling.

Bad example

Bad example

 

Good example

 

 

 

 

 

 

 

 

7. Calculation method of the dimension of the simple quadrate air duct

Presuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side of the air duct is fixed as 250mm, as shown below:

A

Air conditioner

 

AD36NAHBEA

AD242AHBEA

 

AD42NAHBEA

 

AD28NAHBEA

 

AD52NAHBEA

 

 

 

 

Air volume

Duct(mmxmm)

Air volume

Duct(mmxmm)

 

 

 

 

 

A

2400m3/h

250x560

1200m3/h

250x310

 

3

B

A

(40m3/min)

(20m /min)

3

300m3/h

AStatic pressure box Equipped with air filter (bought)

B

600m /h

250x190

(5m3/min)

250x120

(10m3/min)

The calculation of duct resistance (the simple calculation is as follow table)

Straight part

Calculate as per 1m length 1Pa, 1Pa/m

 

 

Bend part

Each bend takes as a3~4m long straight duct

 

 

Air out part

Calculate as 25Pa

Static pressure box

Calculate as 50Pa/each

 

 

Air inlet grille (with air filter)

Calculate as 40Pa/each

The chosen chart of simple duct

Note:1Pa/m=0.1mmAg/m

 

 

 

Shape

Square duct

Item

Dimension

Air volume

 

 

 

m3/h(m3/n)

(mmxmm)

100

250

x

60

200

250

x

90

300

250

x

120

400

250

x

140

500

250

x

170

600(10)

250

x

190

800

250

x

230

1,000

250

x

270

1,200(20)

250

x

310

1,400

250

x

350

1,600

250

x

390

Shape

Square duct

Item

Dimension

Air volume

 

 

 

m3/h(m3/n)

(mmxmm)

1,800(30)

250

x

430

250

x

470

2000

2400

250

x

560

3,000(50)

250

x

650

3,500

250

x

740

4,000

250

x

830

4,500

250

x

920

5,000

250

x

1000

5,500

250

x

1090

6,000(100)

250

x

1180

17

Image 18
Contents Duct Type AIR Conditioner Table of Contents Disposal of the old air conditioner Safety Precations Make sure the system is groundedSafety Precautions Make sure to use a fuse of proper electric ratingMachine is adaptive in following situation Parts and Functions Cooling or heating is not sufficient MalfunctionUnit fails to start Cooling is not sufficientFollowings are not malfunction Care and Maintenance Points to observeFor Preparation of HeatingHot Keep HOT KEEPis operated in the following casesWhen you change your address or the installation place Is The Unit Installed CorrectlyInstallation place For inspection and maintenanceInstallation Manual For Indoor Unit Section as wellChoose installation place Height of ceilingPreparation before installation AD36NAHBEA AD42NAHBEA AD52NAHBEADrain Piping Installation of indoor unitAdjusting to the levelness Good pipingInstallation of air suction and discharging duct ProceduresDrainage Test Chosen chart of simple duct MmxmmM3/hm3/n Mmxmm Examples of improper installation Rotate this switch Operation method of fan controllerRefrigerant pipe Installation Manual For Electric Wiring Wiring connectionPower Supply 1PH,220-230V~,50Hz