Haier AD52NAHBEA, AD242AHBEA, AD36NAHBEA, AD42NAHBEA Machine is adaptive in following situation

Page 6

Safety Precautions

The machine is adaptive in following situation

1. Applicable ambient temperature range:

 

 

 

Rated

Maximum

Minimum

 

Indoor

DB C

27

32

18

Cooling

WB C

19

23

14

 

outdoor

DB C

35

43

10

 

 

WB C

24

26

6

 

 

Heating

Indoor

DB C

20

27

15

WB C

14.5

--

--

 

 

 

outdoor

DB C

7

24

-7

 

 

WB C

6

18

--

2.If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.

3.If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC.

4.The wiring method should be in line with the local wiring standard.

5.The power cable and connecting cable are self-provided. The power cable should be H07RN-F 5G 4.0mm2(for AD52NAHBEA) or

H07RN-F 5G 2.5mm2(forAD28NAHBEA(380-400V, 3N~, 50Hz), AD36NAHBEA, AD42NAHBEA) or

H05RN-F 3G 4.0mm2(for AD242AHBEA).

H05RN-F 3G 6.0mm2(for AD28NAHBEA(1PH, 220-230V~,50Hz)). The connecting cable should be H05RN-F 4G 0.75mm2

All the cables shall have got the European authentication certificate. During installa- tion, when the connecting cables break off, it must be assured that the grouding wire is the last one to be broken off.

6.The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should be no less 3mm.

7.The indoor unit installation height is at least 2.5m.

5

Image 6
Contents Duct Type AIR Conditioner Table of Contents Disposal of the old air conditioner Safety Precations Make sure the system is groundedSafety Precautions Make sure to use a fuse of proper electric ratingMachine is adaptive in following situation Parts and Functions Cooling or heating is not sufficient MalfunctionUnit fails to start Cooling is not sufficientFollowings are not malfunction Care and Maintenance Points to observeFor Preparation of HeatingHot Keep HOT KEEPis operated in the following casesWhen you change your address or the installation place Is The Unit Installed CorrectlyInstallation place For inspection and maintenanceInstallation Manual For Indoor Unit Section as wellChoose installation place Height of ceilingPreparation before installation AD36NAHBEA AD42NAHBEA AD52NAHBEADrain Piping Installation of indoor unitAdjusting to the levelness Good pipingInstallation of air suction and discharging duct ProceduresDrainage Test Chosen chart of simple duct MmxmmM3/hm3/n Mmxmm Examples of improper installation Rotate this switch Operation method of fan controllerRefrigerant pipe Installation Manual For Electric Wiring Wiring connectionPower Supply 1PH,220-230V~,50Hz