Greenheck Fan HRE-45, HRE-20, HRE-90, HRE-55 manual Evaporative Cooling Maintenance

Page 10

EVAPORATIVE COOLING MAINTENANCE

Regularly scheduled maintenance is the key to peak performance, minimized cost, and extended life of the evaporative cooler. The following is a checklist of items that need to be looked at on a regular basis.

1.The media should be checked for mineral and foreign material deposits that have built up. If these items are left on the media, the life and performance of the unit will be greatly reduced. Also, there are risks of water carry over when this type of condition exists. When signs of mineral build-up are noticed, you should increase the bleed off rate. If this does not solve the problem, chemicals may need to be added to the water. The evaporative pads tend to be self cleaning. Depending on water quality and system maintenance, the useful life of the pads should be 3 to 5 years.

2.The media should be periodically brushed lightly with a soft bristle brush in an up and down motion (never brush side-to-side) while flushing with water. This will also aid in reducing the amount of foreign material build-up.

3.The water should be shut off and all the lines drained when the temperature drops below 50°F.

4.When the evaporative cooler is going to be used for the first time each season, it is recommended that the media be flushed with clean water for a period of 2 minutes (see Evap Module Start-Up on page 7).

5.At the beginning of each cooling season, the upright recirculating pump should have the shaft oiled and spun to eliminate the potential of seizing and pump burn out.

6.If the cooling media was removed from the unit, check to make sure that is not installed backwards. If the media is installed backwards, there will be large amounts of water carry over downstream of the evaporative cooler.

Continuous operation in this manner may cause serious damage and void the warranty.

7.At the end of each cooling season the evaporative cooler should be thoroughly cleaned. A dispersant and biocide (consult water treatment consultant for suitable materials and dosage levels) should be recirculated for 12 to 24 hours prior to performing the following steps:

a)Disconnect power to unit.

b)Shut off all water to the unit

c)Open evaporative cooling section door

d)Flush distribution headers and media for 20 minutes

e)Turn off pumps and drain all water distribution piping, headers, etc.

f)Dry media completely by running blowers.

g)Brush media as described in Paragraph 2 and perform steps d and e again.

h)Clean all remaining components (i.e. sump, pump, etc.) of any mineral deposits or foreign materials

i)Replace all worn or non-functioning parts

j)Reassemble the cooling unit.

k)Close cooling section door.

l)Turn the main disconnect 'ON', leaving the cooling switch in the 'OFF' position.

8.If the evaporative cooler will be turned off during the cooling season for an extended period of time, it is recommended that the media be dried out. This can be accomplished by allowing the blowers to continue to run for 1-2 hours. Doing so, will prevent organic build-up on the media and subsequent odors getting into the space.

9.Media should be permitted to dry once per week by allowing the blowers to run for 1-2 hours.

10.A flush cycle should be performed weekly for one hour with the fans off.

10

Image 10
Contents INSTALLATION, Operation and Maintenance Manual Read and Save These InstructionsStorage Table of ContentsGeneral Lifting InstallationRecommended Roof Opening Supply Weatherhood Roof Curb MountingDuct Work Connections Exhaust WeatherhoodElectrical Connections InstallationTypical Control Center Components Service Clearances / Access Panel Locations for Model HRE TOP ViewEvaporative Cooling Modules Evap Module Start-UpWater Control Options for Evaporative Cooling Trouble Shooting for Evaporative Module Symptom SolutionEvaporative Cooling Maintenance Water Coil Application Recommendations Electric Heater APPLICATION/OPERATION Electric PreheaterDirty Filter Switch Setup Frost Control APPLICATION/OPERATIONEconomizer APPLICATION/OPERATION Auto DRY CycleStart UP Checks Pre-Start Check ListFAN RPM Energy Recovery WheelCoils Motors Routine MaintenanceFAN Belts Wheel and FastenersInternal Filter Maintenance External Filter MaintenanceVibration Coil Maintenance Water Coil MaintenanceFilters Routine Energy Recovery Wheel Maintenance Maintenance of the Energy Recovery WheelRemoving the Energy Recovery Wheel Segments Parts List Model HRETrouble Shooting Trouble Shooting Warranty
Related manuals
Manual 44 pages 37.04 Kb

HRE-55, HRE-45, HRE-90, HRE-20 specifications

The Greenheck Fan HRE series, specifically the models HRE-20, HRE-90, HRE-55, and HRE-45, represents a blend of innovation and efficiency in the HVAC industry. Built for both commercial and industrial applications, these exhaust fans stand out due to their robust design and advanced operational features.

One of the main features of the HRE series is its energy-efficient motor design. These fans come equipped with a premium efficiency motor that reduces energy consumption while maintaining high performance. The motors are specifically designed to provide exceptional airflow while operating at lower sound levels, ensuring a quieter environment.

The HRE models also showcase advanced aerodynamic design, featuring optimized blade geometry that enhances airflow performance. This design ensures that the fans can deliver consistent and effective air movement even at varying operational conditions. This makes the HRE series suitable for use in a wide range of applications, from commercial kitchens to industrial processes.

Another significant characteristic of the HRE series is its durability. Constructed from high-quality materials, these fans are built to withstand harsh environmental conditions and prolonged usage. The robust casing and corrosion-resistant finishes ensure longevity, reducing the need for frequent repairs or replacements.

In terms of installation and maintenance, the HRE series offers significant advantages. The fans are designed for easy installation with clear mounting instructions. Additionally, maintenance procedures are simplified, allowing for hassle-free access to critical components, which reduces downtime and operating costs.

Technologically, the HRE models incorporate advanced controls and monitoring systems. These systems can offer real-time feedback on operational performance, allowing for proactive maintenance and energy management. Integrated controls can be customized to work with building management systems, providing users with seamless integration and control capabilities.

Overall, the Greenheck Fan HRE-20, HRE-90, HRE-55, and HRE-45 exemplify a commitment to quality and efficiency in commercial and industrial ventilation solutions. Their combination of energy efficiency, advanced design, durability, and user-friendly features make them a leading choice for those seeking reliable airflow solutions. These fans not only meet current industry standards but also set a benchmark for performance and innovation in the HVAC sector.