Trouble Shooting

Symptom

Possible Cause

Corrective Action

 

 

 

One or Both

Blower fan motor overloads are

Decrease fan speed.

Blowers Turn Off

tripping and auto-resetting.

 

Intermittently and

Exhaust Only frost control

Adjust frost temperature sensor set point as needed.

Back on After

sensors are tripping.

 

About 2 Minutes

 

 

 

 

 

 

 

Air seals are too tight.

See Energy Recovery Wheel on page 16.

 

“Economizer” sensors are

Adjust temperature or enthalpy set points as needed.

Energy Wheel

operating.

 

Does NOT Turn

No power to wheel motor.

Make sure wheel drive is plugged in. Verify power is

 

 

 

available.

 

Wheel drive belt

Check for loose or broken belts. Replace belts (consult

 

 

factory).

 

 

 

Energy Wheel

Wheel motor overloads are

Recheck air seals, make sure they are not too tight. See

tripping, due to rubbing

Energy Recovery Wheel on page 16.

Runs Intermittently

between wheel and air seals.

 

 

 

 

 

 

 

Fan wheel rubbing on inlet

Adjust wheel and/or inlet cone. Tighten wheel hub or bearing

 

 

collars on shaft.

 

Bearings.

Replace defective bearings (s). Lubricate bearings. Tighten

 

 

collars and fasteners.

 

Wheel out of balance.

Replace or rebalance.

 

Loose wheel on shaft.

Tighten wheel setscrew.

 

Loose motor or blower sheave.

Tighten sheave setscrew.

Excessive Noise or

Belts too loose.

Adjust belt tension after 24 hours of operation.

Vibration

Belts too tight.

Loosen to maintain a 3/8 inch deflection per foot of span

 

 

 

between sheaves.

 

Worn belt.

Replace.

 

Motor base or blower loose.

Tighten mounting bolts.

 

Build up of material on wheel.

Clean wheel and housing.

 

Bearing and drive misaligned.

Realign.

 

Noise being transmitted by

Make sure duct work is supported properly. Make sure duct

 

duct.

work metal thickness is sized for proper stiffness. Check duct

 

 

size at discharge to ensure that air velocities are not too high.

* Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating.

Warranty

Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a period of five years from the purchase date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our factory, transportation prepaid.

Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.

Due to continuing product development Greenheck has the right to change specifications without notice

GREENHECK

 

 

P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410

IOM HRE FS

Copyright © 2002 Greenheck Fan Corp.

®

PH. 715-359-6171

Rev. 2, July 2002

www.greenheck.com

Image 24
Contents INSTALLATION, Operation and Maintenance Manual Read and Save These InstructionsTable of Contents StorageGeneral Installation LiftingRecommended Roof Opening Roof Curb Mounting Duct Work ConnectionsSupply Weatherhood Exhaust WeatherhoodInstallation Electrical ConnectionsTypical Control Center Components Service Clearances / Access Panel Locations for Model HRE TOP ViewEvaporative Cooling Modules Evap Module Start-UpWater Control Options for Evaporative Cooling Trouble Shooting for Evaporative Module Symptom SolutionEvaporative Cooling Maintenance Water Coil Application Recommendations Electric Heater APPLICATION/OPERATION Electric PreheaterDirty Filter Switch Setup Frost Control APPLICATION/OPERATIONEconomizer APPLICATION/OPERATION Auto DRY CycleStart UP Checks Pre-Start Check ListEnergy Recovery Wheel FAN RPMCoils Routine Maintenance FAN BeltsMotors Wheel and FastenersExternal Filter Maintenance Internal Filter MaintenanceVibration Water Coil Maintenance Coil MaintenanceFilters Routine Energy Recovery Wheel Maintenance Maintenance of the Energy Recovery WheelRemoving the Energy Recovery Wheel Segments Parts List Model HRETrouble Shooting Trouble Shooting Warranty
Related manuals
Manual 44 pages 37.04 Kb

HRE-55, HRE-45, HRE-90, HRE-20 specifications

The Greenheck Fan HRE series, specifically the models HRE-20, HRE-90, HRE-55, and HRE-45, represents a blend of innovation and efficiency in the HVAC industry. Built for both commercial and industrial applications, these exhaust fans stand out due to their robust design and advanced operational features.

One of the main features of the HRE series is its energy-efficient motor design. These fans come equipped with a premium efficiency motor that reduces energy consumption while maintaining high performance. The motors are specifically designed to provide exceptional airflow while operating at lower sound levels, ensuring a quieter environment.

The HRE models also showcase advanced aerodynamic design, featuring optimized blade geometry that enhances airflow performance. This design ensures that the fans can deliver consistent and effective air movement even at varying operational conditions. This makes the HRE series suitable for use in a wide range of applications, from commercial kitchens to industrial processes.

Another significant characteristic of the HRE series is its durability. Constructed from high-quality materials, these fans are built to withstand harsh environmental conditions and prolonged usage. The robust casing and corrosion-resistant finishes ensure longevity, reducing the need for frequent repairs or replacements.

In terms of installation and maintenance, the HRE series offers significant advantages. The fans are designed for easy installation with clear mounting instructions. Additionally, maintenance procedures are simplified, allowing for hassle-free access to critical components, which reduces downtime and operating costs.

Technologically, the HRE models incorporate advanced controls and monitoring systems. These systems can offer real-time feedback on operational performance, allowing for proactive maintenance and energy management. Integrated controls can be customized to work with building management systems, providing users with seamless integration and control capabilities.

Overall, the Greenheck Fan HRE-20, HRE-90, HRE-55, and HRE-45 exemplify a commitment to quality and efficiency in commercial and industrial ventilation solutions. Their combination of energy efficiency, advanced design, durability, and user-friendly features make them a leading choice for those seeking reliable airflow solutions. These fans not only meet current industry standards but also set a benchmark for performance and innovation in the HVAC sector.