FROST CONTROL APPLICATION/OPERATION

When outdoor air temperatures are extremely cold, moisture condensation and frosting on the energy recovery wheel is possible. Frost control is an optional feature that will prevent wheel frosting. Two options are available:

1)Timed Exhaust frost control and

2)Preheat frost control

Timed exhaust frost control includes a thermostat (with

 

 

 

Indoor RH @ 70°F

Frost Threshold Temp

probe) mounted in the supply air inlet compartment (see

20%

 

2°F

FIGURE 13, page 14) and a timer (Figure 12) mounted in the

 

25%

 

7°F

HRE control center. The thermostat will turn on the timed

 

30%

 

14°F

exhaust frost control feature at a predetermined field

 

 

 

 

adjustable outdoor air temperature (referred to as the Frost

 

TABLE 1

Threshold temperature). The typical temperature setting

 

 

 

corresponds to the indoor air relative humidity as shown in TABLE 1.

 

 

Testing (refer to FIGURE 12)

Set the Timer Scale for T1 and T2 to 1 minute. Set the Timer Settings for T1 and T2 to 1.0. Set the dip switch to the down position.

• Turn the temperature sensor up as high as possible.

 

A1

B1 15

 

The supply blower should cycle on for one minute,

 

 

 

 

 

 

 

 

 

 

 

 

then turn off for one minute.

 

0.8

0.6

 

 

Dip

 

 

 

1.0

0.4

 

 

• After testing, set the Timer Scale as follows: T1 = 10

 

 

 

Switch

 

0

0.2

 

 

 

 

 

 

minutes, T2 = 1 hour

T2

1 MIN T2

 

 

 

 

 

 

 

 

 

• Set the Timer Settings as follows: T1 = 0.5, T2 =

Timer

 

 

 

 

 

0.5. The timer is now set for 5 minutes off and 30

Scale

 

 

 

 

 

minutes on.

 

1 MIN

T1

 

 

 

 

 

 

 

Preheat frost control (see FIGURE 11, page 12) includes a thermostat (with probe) and an electric heater located in the supply air inlet compartment and an air pressure switch in the supply air outlet compartment. The thermostat should be set according to the Frost Threshold temperatures shown in TABLE 1. When the outdoor air temperature reaches the thermostat setting, the electric preheater will turn on and warm the air entering the energy wheel.

0.8 0.6

1.0 0.4 0 0.2

T1

16 18 A2

FIGURE 12

Testing

Turn the thermostat as high as it will go. The heater should turn on.

If it doesn’t, either put the supply side doors on or temporarily jumper the air pressure switch to avoid nuisance tripping of the pressure switch. Remember to remove the jumper.

DIRTY FILTER SWITCH SETUP

This unit may be equipped with a dirty filter switch that functions on differential air pressures to close a relay when the unit filters are clogged and need cleaning. This switch has not been set at the factory due to external system losses that will affect the switch. This switch will need minor field adjustments after the unit has been installed with all ductwork complete. The dirty filter switch is mounted in the exhaust inlet compartment next to the electrical control center.

To adjust the switch the unit must be running with all of the access doors in place, except for the compartment where the switch is located (exhaust inlet compartment). Remove the switch cover plate. The adjusting screw is located on the top of the switch. Open the filter compartment and place a sheet of plastic or cardboard over 50% of the filter media. Replace the filter compartment door. Check to see if there is power at the alert signal leads (refer to electrical diagram). If there is no power, turn the adjustment screw on the dirty filter gage clockwise until you have power. Open the filter compartment and remove the obstructing material. Replace the door and check to make sure that you do not have power at the alert signal leads. The unit is now ready for operation.

13

Image 13
Contents Read and Save These Instructions INSTALLATION, Operation and Maintenance ManualStorage Table of ContentsGeneral Lifting InstallationRecommended Roof Opening Duct Work Connections Roof Curb MountingSupply Weatherhood Exhaust WeatherhoodElectrical Connections InstallationTypical Control Center Components TOP View Service Clearances / Access Panel Locations for Model HREEvap Module Start-Up Evaporative Cooling ModulesWater Control Options for Evaporative Cooling Symptom Solution Trouble Shooting for Evaporative ModuleEvaporative Cooling Maintenance Water Coil Application Recommendations Electric Preheater Electric Heater APPLICATION/OPERATIONFrost Control APPLICATION/OPERATION Dirty Filter Switch SetupAuto DRY Cycle Economizer APPLICATION/OPERATIONPre-Start Check List Start UP ChecksFAN RPM Energy Recovery WheelCoils FAN Belts Routine MaintenanceMotors Wheel and FastenersInternal Filter Maintenance External Filter MaintenanceVibration Coil Maintenance Water Coil MaintenanceFilters Maintenance of the Energy Recovery Wheel Routine Energy Recovery Wheel MaintenanceRemoving the Energy Recovery Wheel Segments Model HRE Parts ListTrouble Shooting Warranty Trouble Shooting
Related manuals
Manual 44 pages 37.04 Kb

HRE-55, HRE-45, HRE-90, HRE-20 specifications

The Greenheck Fan HRE series, specifically the models HRE-20, HRE-90, HRE-55, and HRE-45, represents a blend of innovation and efficiency in the HVAC industry. Built for both commercial and industrial applications, these exhaust fans stand out due to their robust design and advanced operational features.

One of the main features of the HRE series is its energy-efficient motor design. These fans come equipped with a premium efficiency motor that reduces energy consumption while maintaining high performance. The motors are specifically designed to provide exceptional airflow while operating at lower sound levels, ensuring a quieter environment.

The HRE models also showcase advanced aerodynamic design, featuring optimized blade geometry that enhances airflow performance. This design ensures that the fans can deliver consistent and effective air movement even at varying operational conditions. This makes the HRE series suitable for use in a wide range of applications, from commercial kitchens to industrial processes.

Another significant characteristic of the HRE series is its durability. Constructed from high-quality materials, these fans are built to withstand harsh environmental conditions and prolonged usage. The robust casing and corrosion-resistant finishes ensure longevity, reducing the need for frequent repairs or replacements.

In terms of installation and maintenance, the HRE series offers significant advantages. The fans are designed for easy installation with clear mounting instructions. Additionally, maintenance procedures are simplified, allowing for hassle-free access to critical components, which reduces downtime and operating costs.

Technologically, the HRE models incorporate advanced controls and monitoring systems. These systems can offer real-time feedback on operational performance, allowing for proactive maintenance and energy management. Integrated controls can be customized to work with building management systems, providing users with seamless integration and control capabilities.

Overall, the Greenheck Fan HRE-20, HRE-90, HRE-55, and HRE-45 exemplify a commitment to quality and efficiency in commercial and industrial ventilation solutions. Their combination of energy efficiency, advanced design, durability, and user-friendly features make them a leading choice for those seeking reliable airflow solutions. These fans not only meet current industry standards but also set a benchmark for performance and innovation in the HVAC sector.