Page 22

COOLING PERFORMANCE DATA

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown. A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

22

Image 22
Contents Technical Manual Goodman will not be responsible Product IdentificationFor any injury or property damage GPC1524M41A GPC1530M41A GPC1536M41A GPC1542M41A GPC1548M41A Product Design Location and ClearancesRooftop Installation Multi-positional M GPC1524-48M41 HKR Electrical DataProduct Dimensions Control Connection Wire NPT Female EntranceGPC1524-48M41A ElectricalAccessories Accessories GPC/GPH****M ModelsBlower Performance Data Performance Data Formulas105 115 Cooling Performance DataGPC1524M41 21.2KW = Total system power 147GPC1530M41 AirflowExpanded Performance Data 146GPC1536M41 148 GPC1542M41 152 Is Ahri Rating Conditions KW =GPC1548M41 45.5 Performance Test Wiring Diagrams HKRGPC1524-48M41 Diagrams Wiring